  "boundary": "Electrical supply, stored battery energy, conversion losses and served IT; cooling excluded",
  "engine_version": "1.0.0",
  "events": [
    {
      "action": "asset_down",
      "at_s": "300",
      "origin": "scenario_event",
      "sequence": 0,
      "target": "path-a",
      "value_kw": null
    },
    {
      "action": "asset_up",
      "at_s": "900",
      "origin": "scenario_event",
      "sequence": 1,
      "target": "path-a",
      "value_kw": null
    }
  ],
  "input_sha256": "6b446789e2f755b9ac1ac81896c7f0d85827a9a03b6ceedfd8fbdc6cb3b775dd",
  "intervals": [
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "10",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "0.29",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "0",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "20",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "0.58",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "10",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "30",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "0.88",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "20",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "40",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "1.17",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "30",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "50",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "1.46",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "40",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "60",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "1.75",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "50",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "70",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "2.05",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "60",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "80",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "2.34",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "70",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "90",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "2.63",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "80",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "100",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "2.92",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "90",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "110",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "3.22",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "100",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "120",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "3.51",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "110",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "130",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "3.80",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "120",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "140",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "4.09",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "130",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "150",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "4.39",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "140",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "160",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "4.68",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "150",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "170",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "4.97",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "160",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "180",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "5.26",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "170",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "190",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "5.56",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "180",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "200",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "5.85",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "190",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "210",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "6.14",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "200",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "220",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "6.43",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "210",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "230",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "6.73",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "220",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "240",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "7.02",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "230",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "250",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "7.31",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "240",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "260",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "7.60",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "250",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "270",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "7.89",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "260",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "280",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "8.19",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "270",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "290",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "8.48",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "280",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "300",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "8.77",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "290",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "310",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "8.97",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "300",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "320",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "9.16",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "310",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "330",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "9.36",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "320",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "340",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "9.55",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "330",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "350",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "9.74",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "340",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "360",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "9.94",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "350",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "370",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "10.13",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "360",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "380",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "10.33",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "370",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "390",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "10.52",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "380",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "400",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "10.72",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "390",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "410",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "10.91",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "400",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "420",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "11.11",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "410",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "430",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "11.30",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "420",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "440",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "11.49",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "430",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "450",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "11.69",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "440",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "460",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "11.88",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "450",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "470",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "12.08",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "460",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "480",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "12.27",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "470",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "490",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "12.47",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "480",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "500",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "12.66",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "490",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "510",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "12.86",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "500",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "520",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "13.05",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "510",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "530",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "13.24",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "520",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "540",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "13.44",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "530",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "550",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "13.63",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "540",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "560",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "13.83",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "550",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "570",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "14.02",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "560",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "580",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "14.22",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "570",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "590",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "14.41",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "580",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "600",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "14.61",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "590",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "610",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "14.80",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "600",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "620",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "14.99",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "610",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "630",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "15.19",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "620",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "640",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "15.38",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "630",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "650",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "15.58",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "640",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "660",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "15.77",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "650",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "670",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "15.97",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "660",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "680",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "16.16",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "670",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "690",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "16.36",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "680",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "700",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "16.55",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "690",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "710",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "16.74",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "700",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "720",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "16.94",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "710",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "730",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "17.13",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "720",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "740",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "17.33",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "730",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "750",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "17.52",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "740",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "760",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "17.72",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "750",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "770",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "17.91",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "760",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "780",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "18.11",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "770",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "790",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "18.30",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "780",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "800",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "18.49",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "790",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "810",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "18.69",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "800",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "820",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "18.88",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "810",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "830",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "19.08",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "820",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "840",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "19.27",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "830",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "850",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "19.47",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "840",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "860",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "19.66",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "850",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "870",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "19.86",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "860",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "880",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "20.05",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "870",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "890",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "20.24",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "880",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "degraded",
        "main-bus": "available",
        "path-a": "unavailable",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "700",
      "end_s": "900",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "generator_kwh": "0",
        "grid_kwh": "1.944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
        "unserved_duration_s": "10",
        "unserved_it_kwh": "0.9305555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "700",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "0",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "700",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "20.44",
      "grid_kw": "700",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "665",
      "start_s": "890",
      "unserved_it_kw": "335",
      "warnings": [
        "UNSERVED_IT_LOAD"
      ]
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "910",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "20.73",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "900",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "920",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "21.02",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "910",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "930",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "21.32",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "920",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "940",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "21.61",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "930",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "950",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "21.90",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "940",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "960",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "22.19",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "950",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "970",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "22.49",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "960",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "980",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "22.78",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "970",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "990",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "23.07",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "980",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1000",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "23.36",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "990",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1010",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "23.65",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1000",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1020",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "23.95",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1010",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1030",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "24.24",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1020",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1040",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "24.53",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1030",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1050",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "24.82",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1040",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1060",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "25.12",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1050",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1070",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "25.41",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1060",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1080",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "25.70",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1070",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1090",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "25.99",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1080",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1100",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "26.29",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1090",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1110",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "26.58",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1100",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1120",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "26.87",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1110",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1130",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "27.16",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1120",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1140",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "27.46",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1130",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1150",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "27.75",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1140",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1160",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "28.04",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1150",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1170",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "28.33",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1160",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1180",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "28.63",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1170",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1190",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "28.92",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1180",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1200",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "29.21",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1190",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1210",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "29.50",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1200",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1220",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "29.80",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1210",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1230",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "30.09",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1220",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1240",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "30.38",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1230",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1250",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "30.67",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1240",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1260",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "30.96",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1250",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1270",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "31.26",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1260",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1280",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "31.55",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1270",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1290",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "31.84",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1280",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1300",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "32.13",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1290",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1310",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "32.43",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1300",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1320",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "32.72",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1310",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1330",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "33.01",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1320",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1340",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "33.30",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1330",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1350",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "33.60",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1340",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1360",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "33.89",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1350",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1370",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "34.18",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1360",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1380",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "34.47",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1370",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1390",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "34.77",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1380",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1400",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "35.06",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1390",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1410",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "35.35",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1400",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1420",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "35.64",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1410",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1430",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "35.94",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1420",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1440",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "36.23",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1430",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1450",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "36.52",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1440",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1460",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "36.81",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1450",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1470",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "37.11",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1460",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1480",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "37.40",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1470",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1490",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "37.69",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1480",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1500",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "37.98",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1490",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1510",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "38.27",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1500",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1520",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "38.57",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1510",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1530",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "38.86",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1520",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1540",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "39.15",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1530",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1550",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "39.44",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1540",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1560",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "39.74",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1550",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1570",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "40.03",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1560",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1580",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "40.32",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1570",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1590",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "40.61",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1580",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1600",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "40.91",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1590",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1610",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "41.20",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1600",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1620",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "41.49",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1610",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1630",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "41.78",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1620",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1640",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "42.08",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1630",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1650",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "42.37",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1640",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1660",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "42.66",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1650",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1670",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "42.95",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1660",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1680",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "43.25",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1670",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1690",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "43.54",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1680",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1700",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "43.83",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1690",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1710",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "44.12",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1700",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1720",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "44.42",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1710",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1730",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "44.71",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1720",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1740",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "45.00",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1730",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1750",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "45.29",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1740",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1760",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "45.58",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1750",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1770",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "45.88",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1760",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1780",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "46.17",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1770",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1790",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "46.46",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1780",
      "unserved_it_kw": "0",
      "warnings": []
    },
    {
      "asset_states": {
        "battery": "ready",
        "generator": "standby",
        "it-bus": "available",
        "it-load": "served",
        "main-bus": "available",
        "path-a": "available",
        "path-b": "available",
        "utility": "available"
      },
      "battery_charge_kw": "0",
      "battery_discharge_kw": "0",
      "battery_end_kwh": "100",
      "battery_start_kwh": "100",
      "duration_s": "10",
      "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "end_s": "1800",
      "energy": {
        "battery_charge_loss_kwh": "0",
        "battery_discharge_loss_kwh": "0",
        "battery_stored_change_kwh": "0",
        "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
        "generator_kwh": "0",
        "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
        "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
        "unserved_duration_s": "0",
        "unserved_it_kwh": "0"
      },
      "energy_balance_residual_kwh": "0",
      "feed_flows_kw": [
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "utility",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "generator",
          "target": "main-bus"
        },
        {
          "kw": "0",
          "source": "battery",
          "target": "main-bus"
        },
        {
          "kw": "700",
          "source": "main-bus",
          "target": "path-a"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "main-bus",
          "target": "path-b"
        },
        {
          "kw": "700",
          "source": "path-a",
          "target": "it-bus"
        },
        {
          "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789",
          "source": "path-b",
          "target": "it-bus"
        },
        {
          "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
          "source": "it-bus",
          "target": "it-load"
        }
      ],
      "generator_kw": "0",
      "grid_energy_charge_to_date": "46.75",
      "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
      "it_capacity_margin_kw": "0",
      "requested_it_kw": "1000",
      "served_it_kw": "1000",
      "start_s": "1790",
      "unserved_it_kw": "0",
      "warnings": []
    }
  ],
  "limitations": [
    "No switching transient, protection study, cooling, workload queue or certification model.",
    "Generator starts on utility-asset unavailability only; downstream path faults do not request a start.",
    "Generator fuel is assumed sufficient for this horizon; its unit energy cost may be unknown.",
    "Initial stored battery energy is an opening balance; prior charging cost is excluded.",
    "Prices are illustrative inputs; costs exclude CAPEX and non-energy charges."
  ],
  "mode": "SIMULATED",
  "model": "single_load_electrical_continuity_v1",
  "quality": "synthetic_uncalibrated",
  "run_id": "bdbd07fc183ea54c6cba",
  "scenario": {
    "assets": [
      {
        "capacity_kw": "1500",
        "failure_domains": [
          "utility-feed"
        ],
        "id": "utility",
        "kind": "utility",
        "name": "Utility feed",
        "source_ids": [
          "DEMO-ELECTRICAL-002"
        ]
      },
      {
        "capacity_kw": "1200",
        "failure_domains": [
          "generator-control"
        ],
        "id": "generator",
        "kind": "generator",
        "name": "Standby generator",
        "source_ids": [
          "DEMO-ELECTRICAL-002"
        ]
      },
      {
        "capacity_kw": "1200",
        "failure_domains": [
          "ups-control"
        ],
        "id": "battery",
        "kind": "battery",
        "name": "UPS battery",
        "source_ids": [
          "DEMO-ELECTRICAL-002"
        ]
      },
      {
        "capacity_kw": "1800",
        "failure_domains": [
          "switchroom"
        ],
        "id": "main-bus",
        "kind": "bus",
        "name": "Main electrical bus",
        "source_ids": [
          "DEMO-ELECTRICAL-002"
        ]
      },
      {
        "capacity_kw": "700",
        "failure_domains": [
          "a-room",
          "shared-controls"
        ],
        "id": "path-a",
        "kind": "distribution",
        "name": "Distribution A",
        "source_ids": [
          "DEMO-ELECTRICAL-002"
        ]
      },
      {
        "capacity_kw": "700",
        "failure_domains": [
          "b-room",
          "shared-controls"
        ],
        "id": "path-b",
        "kind": "distribution",
        "name": "Distribution B",
        "source_ids": [
          "DEMO-ELECTRICAL-002"
        ]
      },
      {
        "capacity_kw": "1800",
        "failure_domains": [
          "it-bus"
        ],
        "id": "it-bus",
        "kind": "bus",
        "name": "IT distribution bus",
        "source_ids": [
          "DEMO-ELECTRICAL-002"
        ]
      },
      {
        "capacity_kw": "2000",
        "failure_domains": [
          "it-hall"
        ],
        "id": "it-load",
        "kind": "load",
        "name": "Synthetic IT demand",
        "source_ids": [
          "DEMO-ELECTRICAL-002"
        ]
      }
    ],
    "battery_capacity_kwh": "100",
    "battery_charge_efficiency": "0.95",
    "battery_charge_kw": "100",
    "battery_discharge_efficiency": "0.9",
    "battery_initial_kwh": "100",
    "currency": "USD",
    "dependencies": [
      {
        "relation": "feeds",
        "source": "utility",
        "target": "main-bus"
      },
      {
        "relation": "feeds",
        "source": "generator",
        "target": "main-bus"
      },
      {
        "relation": "feeds",
        "source": "battery",
        "target": "main-bus"
      },
      {
        "relation": "feeds",
        "source": "main-bus",
        "target": "path-a"
      },
      {
        "relation": "feeds",
        "source": "main-bus",
        "target": "path-b"
      },
      {
        "relation": "feeds",
        "source": "path-a",
        "target": "it-bus"
      },
      {
        "relation": "feeds",
        "source": "path-b",
        "target": "it-bus"
      },
      {
        "relation": "feeds",
        "source": "it-bus",
        "target": "it-load"
      },
      {
        "relation": "charges",
        "source": "main-bus",
        "target": "battery"
      }
    ],
    "distribution_efficiency": "0.95",
    "duration_s": 1800,
    "events": [
      {
        "action": "asset_down",
        "at_s": 300,
        "target": "path-a",
        "value_kw": null
      },
      {
        "action": "asset_up",
        "at_s": 900,
        "target": "path-a",
        "value_kw": null
      }
    ],
    "generator_cost_per_kwh": null,
    "generator_start_delay_s": 30,
    "id": "demo-path_maintenance",
    "it_capacity_kw": "1000",
    "it_demand_kw": "1000",
    "name": "A-path maintenance / surviving overload",
    "schema_version": 2,
    "source_ids": [
      "DEMO-ELECTRICAL-002"
    ],
    "step_s": 10,
    "tariff_per_kwh": "0.1"
  },
  "schema_version": 2,
  "summary": {
    "battery_charge_loss_kwh": "0",
    "battery_discharge_loss_kwh": "0",
    "battery_final_kwh": "100",
    "battery_stored_change_kwh": "0",
    "cost_status": "illustrative",
    "distribution_loss_kwh": "23.37719298245614035087719298245614035087719298245614035087719298245614035087719298245614035087719298",
    "energy_balance_residual_kwh": "0",
    "generator_energy_charge": "0.00",
    "generator_kwh": "0",
    "grid_energy_charge": "46.75",
    "grid_kwh": "467.5438596491228070175438596491228070175438596491228070175438596491228070175438596491228070175438596",
    "interval_count": 180,
    "peak_unserved_kw": "335",
    "requested_it_kwh": "500",
    "served_it_kwh": "444.1666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
    "service_status": "unserved_load",
    "total_incremental_energy_charge": "46.75",
    "unserved_duration_s": "600",
    "unserved_it_kwh": "55.83333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333"
  }
}