  "schema_version": 1,
  "lesson_id": "generator-failure",
  "lesson_url": "https://khanlab.co.technology/learn/generator-failure/",
  "engine_version": "2.0.1",
  "source_revision": "4878472c4d6c166c3dbd81aee292a0a56e89ffff",
  "result_unit": "s unserved",
  "records": [
    {
      "configuration": "starting",
      "input": "0",
      "result": "292.2",
      "unit": "s unserved",
      "calculation": {
        "schema_version": 2,
        "model": "single_load_electrical_continuity_v1",
        "engine_version": "2.0.1",
        "run_id": "0b90988440023df580eb",
        "input_sha256": "2ec2db9c126b1e11de686e6498ee6ae5be29b80ba11ab7581fffd4765bf44dcd",
        "mode": "SIMULATED",
        "quality": "synthetic_uncalibrated",
        "scenario": {
          "schema_version": 2,
          "id": "course-generator-failure",
          "name": "5. Add a failed generator",
          "currency": "USD",
          "duration_s": 1800,
          "step_s": 10,
          "it_demand_kw": "1000",
          "it_capacity_kw": "1000",
          "distribution_efficiency": "0.95",
          "tariff_per_kwh": "0.1",
          "generator_cost_per_kwh": null,
          "generator_start_delay_s": 30,
          "battery_capacity_kwh": "100",
          "battery_initial_kwh": "100",
          "battery_charge_kw": "100",
          "battery_charge_efficiency": "0.95",
          "battery_discharge_efficiency": "0.9",
          "source_ids": [
            "DEMO-ELECTRICAL-002",
            "EDU-POWER-001"
          ],
          "assets": [
            {
              "id": "utility",
              "name": "Utility feed",
              "kind": "utility",
              "capacity_kw": "1500",
              "failure_domains": [
                "utility-feed"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "generator",
              "name": "Standby generator",
              "kind": "generator",
              "capacity_kw": "1200",
              "failure_domains": [
                "generator-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "battery",
              "name": "UPS battery",
              "kind": "battery",
              "capacity_kw": "1200",
              "failure_domains": [
                "ups-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "main-bus",
              "name": "Main electrical bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "switchroom"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-a",
              "name": "Distribution A",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "a-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-b",
              "name": "Distribution B",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "b-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-bus",
              "name": "IT distribution bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "it-bus"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-load",
              "name": "Synthetic IT demand",
              "kind": "load",
              "capacity_kw": "2000",
              "failure_domains": [
                "it-hall"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            }
          ],
          "dependencies": [
            {
              "source": "utility",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "generator",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "battery",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-a",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-b",
              "relation": "feeds"
            },
            {
              "source": "path-a",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "path-b",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "it-bus",
              "target": "it-load",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "battery",
              "relation": "charges"
            }
          ],
          "events": [
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "generator",
              "value_kw": null
            },
            {
              "at_s": 900,
              "action": "asset_up",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 900,
              "action": "asset_up",
              "target": "generator",
              "value_kw": null
            }
          ]
        },
        "intervals": [
          {
            "start_s": "0",
            "end_s": "10",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "10",
            "end_s": "20",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "20",
            "end_s": "30",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.88",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "30",
            "end_s": "40",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.17",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "40",
            "end_s": "50",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "50",
            "end_s": "60",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.75",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "60",
            "end_s": "70",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "70",
            "end_s": "80",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "80",
            "end_s": "90",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.63",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "90",
            "end_s": "100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.92",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "100",
            "end_s": "110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "110",
            "end_s": "120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.51",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "120",
            "end_s": "130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.80",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "130",
            "end_s": "140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "140",
            "end_s": "150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.39",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "150",
            "end_s": "160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.68",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "160",
            "end_s": "170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.97",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "170",
            "end_s": "180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.26",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "180",
            "end_s": "190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.56",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "190",
            "end_s": "200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.85",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "200",
            "end_s": "210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "210",
            "end_s": "220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.43",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "220",
            "end_s": "230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "230",
            "end_s": "240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "240",
            "end_s": "250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.31",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "250",
            "end_s": "260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.60",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "260",
            "end_s": "270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "270",
            "end_s": "280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.19",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "280",
            "end_s": "290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.48",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "290",
            "end_s": "300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "300",
            "end_s": "310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "96.7511371020142949967511371020142949967511371020142949967511371020142949967511371020142949967511371",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "310",
            "end_s": "320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "96.7511371020142949967511371020142949967511371020142949967511371020142949967511371020142949967511371",
            "battery_end_kwh": "93.5022742040285899935022742040285899935022742040285899935022742040285899935022742040285899935022742",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "320",
            "end_s": "330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "93.5022742040285899935022742040285899935022742040285899935022742040285899935022742040285899935022742",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "330",
            "end_s": "340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "87.00454840805717998700454840805717998700454840805717998700454840805717998700454840805717998700454841",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "340",
            "end_s": "350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "87.00454840805717998700454840805717998700454840805717998700454840805717998700454840805717998700454841",
            "battery_end_kwh": "83.75568551007147498375568551007147498375568551007147498375568551007147498375568551007147498375568551",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "350",
            "end_s": "360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "83.75568551007147498375568551007147498375568551007147498375568551007147498375568551007147498375568551",
            "battery_end_kwh": "80.50682261208576998050682261208576998050682261208576998050682261208576998050682261208576998050682261",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "360",
            "end_s": "370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "80.50682261208576998050682261208576998050682261208576998050682261208576998050682261208576998050682261",
            "battery_end_kwh": "77.25795971410006497725795971410006497725795971410006497725795971410006497725795971410006497725795971",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "370",
            "end_s": "380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "77.25795971410006497725795971410006497725795971410006497725795971410006497725795971410006497725795971",
            "battery_end_kwh": "74.00909681611435997400909681611435997400909681611435997400909681611435997400909681611435997400909682",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "380",
            "end_s": "390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "74.00909681611435997400909681611435997400909681611435997400909681611435997400909681611435997400909682",
            "battery_end_kwh": "70.76023391812865497076023391812865497076023391812865497076023391812865497076023391812865497076023392",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "390",
            "end_s": "400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "70.76023391812865497076023391812865497076023391812865497076023391812865497076023391812865497076023392",
            "battery_end_kwh": "67.51137102014294996751137102014294996751137102014294996751137102014294996751137102014294996751137102",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "400",
            "end_s": "410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "67.51137102014294996751137102014294996751137102014294996751137102014294996751137102014294996751137102",
            "battery_end_kwh": "64.26250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426250812",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "410",
            "end_s": "420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "64.26250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426250812",
            "battery_end_kwh": "61.01364522417153996101364522417153996101364522417153996101364522417153996101364522417153996101364522",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "420",
            "end_s": "430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "61.01364522417153996101364522417153996101364522417153996101364522417153996101364522417153996101364522",
            "battery_end_kwh": "57.76478232618583495776478232618583495776478232618583495776478232618583495776478232618583495776478233",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "430",
            "end_s": "440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "57.76478232618583495776478232618583495776478232618583495776478232618583495776478232618583495776478233",
            "battery_end_kwh": "54.51591942820012995451591942820012995451591942820012995451591942820012995451591942820012995451591943",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "440",
            "end_s": "450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "54.51591942820012995451591942820012995451591942820012995451591942820012995451591942820012995451591943",
            "battery_end_kwh": "51.26705653021442495126705653021442495126705653021442495126705653021442495126705653021442495126705653",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "450",
            "end_s": "460",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "51.26705653021442495126705653021442495126705653021442495126705653021442495126705653021442495126705653",
            "battery_end_kwh": "48.01819363222871994801819363222871994801819363222871994801819363222871994801819363222871994801819363",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "460",
            "end_s": "470",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "48.01819363222871994801819363222871994801819363222871994801819363222871994801819363222871994801819363",
            "battery_end_kwh": "44.76933073424301494476933073424301494476933073424301494476933073424301494476933073424301494476933073",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "470",
            "end_s": "480",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "44.76933073424301494476933073424301494476933073424301494476933073424301494476933073424301494476933073",
            "battery_end_kwh": "41.52046783625730994152046783625730994152046783625730994152046783625730994152046783625730994152046784",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "480",
            "end_s": "490",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "41.52046783625730994152046783625730994152046783625730994152046783625730994152046783625730994152046784",
            "battery_end_kwh": "38.27160493827160493827160493827160493827160493827160493827160493827160493827160493827160493827160494",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "490",
            "end_s": "500",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "38.27160493827160493827160493827160493827160493827160493827160493827160493827160493827160493827160494",
            "battery_end_kwh": "35.02274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "500",
            "end_s": "510",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "35.02274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "31.77387914230019493177387914230019493177387914230019493177387914230019493177387914230019493177387914",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "510",
            "end_s": "520",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "31.77387914230019493177387914230019493177387914230019493177387914230019493177387914230019493177387914",
            "battery_end_kwh": "28.52501624431448992852501624431448992852501624431448992852501624431448992852501624431448992852501624",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "520",
            "end_s": "530",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "28.52501624431448992852501624431448992852501624431448992852501624431448992852501624431448992852501624",
            "battery_end_kwh": "25.27615334632878492527615334632878492527615334632878492527615334632878492527615334632878492527615335",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "530",
            "end_s": "540",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "25.27615334632878492527615334632878492527615334632878492527615334632878492527615334632878492527615335",
            "battery_end_kwh": "22.02729044834307992202729044834307992202729044834307992202729044834307992202729044834307992202729045",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "540",
            "end_s": "550",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "22.02729044834307992202729044834307992202729044834307992202729044834307992202729044834307992202729045",
            "battery_end_kwh": "18.77842755035737491877842755035737491877842755035737491877842755035737491877842755035737491877842755",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "550",
            "end_s": "560",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "18.77842755035737491877842755035737491877842755035737491877842755035737491877842755035737491877842755",
            "battery_end_kwh": "15.52956465237166991552956465237166991552956465237166991552956465237166991552956465237166991552956465",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "560",
            "end_s": "570",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "15.52956465237166991552956465237166991552956465237166991552956465237166991552956465237166991552956465",
            "battery_end_kwh": "12.28070175438596491228070175438596491228070175438596491228070175438596491228070175438596491228070175",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "570",
            "end_s": "580",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "12.28070175438596491228070175438596491228070175438596491228070175438596491228070175438596491228070175",
            "battery_end_kwh": "9.031838856400259909031838856400259909031838856400259909031838856400259909031838856400259909031838856",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "580",
            "end_s": "590",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "9.031838856400259909031838856400259909031838856400259909031838856400259909031838856400259909031838856",
            "battery_end_kwh": "5.782975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782975958",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "590",
            "end_s": "600",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "5.782975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782975958",
            "battery_end_kwh": "2.53411306042884990253411306042884990253411306042884990253411306042884990253411306042884990253411306",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "600",
            "end_s": "607.8",
            "duration_s": "7.8",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "2.53411306042884990253411306042884990253411306042884990253411306042884990253411306042884990253411306",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
              "served_it_kwh": "2.166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1140350877192982456140350877192982456140350877192982456140350877192982456140350877192982456140350877",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.253411306042884990253411306042884990253411306042884990253411306042884990253411306042884990253411306",
              "battery_stored_change_kwh": "-2.53411306042884990253411306042884990253411306042884990253411306042884990253411306042884990253411306",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "607.8",
            "end_s": "617.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "617.8",
            "end_s": "627.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "627.8",
            "end_s": "637.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "637.8",
            "end_s": "647.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "647.8",
            "end_s": "657.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "657.8",
            "end_s": "667.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "667.8",
            "end_s": "677.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "677.8",
            "end_s": "687.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "687.8",
            "end_s": "697.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "697.8",
            "end_s": "707.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "707.8",
            "end_s": "717.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "717.8",
            "end_s": "727.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "727.8",
            "end_s": "737.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "737.8",
            "end_s": "747.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "747.8",
            "end_s": "757.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "757.8",
            "end_s": "767.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "767.8",
            "end_s": "777.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "777.8",
            "end_s": "787.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "787.8",
            "end_s": "797.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "797.8",
            "end_s": "807.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "807.8",
            "end_s": "817.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "817.8",
            "end_s": "827.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "827.8",
            "end_s": "837.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "837.8",
            "end_s": "847.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "847.8",
            "end_s": "857.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "857.8",
            "end_s": "867.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "867.8",
            "end_s": "877.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "877.8",
            "end_s": "887.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "887.8",
            "end_s": "897.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "897.8",
            "end_s": "900",
            "duration_s": "2.2",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "0.6111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
              "served_it_kwh": "0",
              "unserved_it_kwh": "0.6111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "2.2"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "900",
            "end_s": "910",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "910",
            "end_s": "920",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "0.5277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.41",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "920",
            "end_s": "930",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "0.5277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "0.7916666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "930",
            "end_s": "940",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "0.7916666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "1.055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "940",
            "end_s": "950",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "1.319444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.37",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "950",
            "end_s": "960",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.319444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "1.583333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.69",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "960",
            "end_s": "970",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.583333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.01",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "970",
            "end_s": "980",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "2.111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.33",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "980",
            "end_s": "990",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "2.375",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.65",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "990",
            "end_s": "1000",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.375",
            "battery_end_kwh": "2.638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.97",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1000",
            "end_s": "1010",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "2.902777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1010",
            "end_s": "1020",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.902777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "3.166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1020",
            "end_s": "1030",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "3.430555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.93",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1030",
            "end_s": "1040",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.430555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "3.694444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1040",
            "end_s": "1050",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.694444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "3.958333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1050",
            "end_s": "1060",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.958333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "4.222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1060",
            "end_s": "1070",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "4.222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "4.486111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.21",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1070",
            "end_s": "1080",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "4.486111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "4.75",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1080",
            "end_s": "1090",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "4.75",
            "battery_end_kwh": "5.013888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1090",
            "end_s": "1100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.013888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "5.277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1100",
            "end_s": "1110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "5.541666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1110",
            "end_s": "1120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.541666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "5.805555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1120",
            "end_s": "1130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.805555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "6.069444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1130",
            "end_s": "1140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.069444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "6.333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1140",
            "end_s": "1150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "6.597222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.78",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1150",
            "end_s": "1160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.597222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "6.861111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.10",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1160",
            "end_s": "1170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.861111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "7.125",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.42",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1170",
            "end_s": "1180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.125",
            "battery_end_kwh": "7.388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.74",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1180",
            "end_s": "1190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "7.652777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.06",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1190",
            "end_s": "1200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.652777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "7.916666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.38",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1200",
            "end_s": "1210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.916666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "8.180555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1210",
            "end_s": "1220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.180555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "8.444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1220",
            "end_s": "1230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "8.708333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1230",
            "end_s": "1240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.708333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "8.972222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.66",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1240",
            "end_s": "1250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.972222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "9.236111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.98",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1250",
            "end_s": "1260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "9.236111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "9.5",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.30",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1260",
            "end_s": "1270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "9.5",
            "battery_end_kwh": "9.763888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.62",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1270",
            "end_s": "1280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "9.763888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "10.02777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.94",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1280",
            "end_s": "1290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.02777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "10.29166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.26",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1290",
            "end_s": "1300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.29166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "10.55555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1300",
            "end_s": "1310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.55555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "10.81944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.90",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1310",
            "end_s": "1320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.81944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "11.08333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1320",
            "end_s": "1330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.08333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "11.34722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1330",
            "end_s": "1340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.34722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "11.61111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1340",
            "end_s": "1350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.61111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "11.875",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1350",
            "end_s": "1360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.875",
            "battery_end_kwh": "12.13888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1360",
            "end_s": "1370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.13888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "12.40277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1370",
            "end_s": "1380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.40277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "12.66666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1380",
            "end_s": "1390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.66666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "12.93055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1390",
            "end_s": "1400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.93055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "13.19444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.78",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1400",
            "end_s": "1410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.19444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "13.45833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.10",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1410",
            "end_s": "1420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.45833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "13.72222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.42",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1420",
            "end_s": "1430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.72222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "13.98611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.74",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1430",
            "end_s": "1440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.98611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "14.25",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.06",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1440",
            "end_s": "1450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "14.25",
            "battery_end_kwh": "14.51388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.38",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1450",
            "end_s": "1460",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "14.51388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "14.77777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1460",
            "end_s": "1470",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "14.77777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "15.04166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1470",
            "end_s": "1480",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.04166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "15.30555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1480",
            "end_s": "1490",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.30555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "15.56944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.66",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1490",
            "end_s": "1500",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.56944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "15.83333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.98",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1500",
            "end_s": "1510",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.83333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "16.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.30",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1510",
            "end_s": "1520",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "16.36111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.62",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1520",
            "end_s": "1530",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.36111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "16.625",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.94",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1530",
            "end_s": "1540",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.625",
            "battery_end_kwh": "16.88888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.26",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1540",
            "end_s": "1550",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.88888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "17.15277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1550",
            "end_s": "1560",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.15277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "17.41666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.90",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1560",
            "end_s": "1570",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.41666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "17.68055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1570",
            "end_s": "1580",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.68055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "17.94444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1580",
            "end_s": "1590",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.94444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "18.20833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1590",
            "end_s": "1600",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "18.20833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "18.47222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1600",
            "end_s": "1610",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "18.47222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "18.73611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1610",
            "end_s": "1620",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "18.73611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "19",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1620",
            "end_s": "1630",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19",
            "battery_end_kwh": "19.26388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1630",
            "end_s": "1640",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19.26388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "19.52777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1640",
            "end_s": "1650",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19.52777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "19.79166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.79",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1650",
            "end_s": "1660",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19.79166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "20.05555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.11",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1660",
            "end_s": "1670",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.05555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "20.31944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.43",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1670",
            "end_s": "1680",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.31944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "20.58333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.75",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1680",
            "end_s": "1690",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.58333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "20.84722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.07",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1690",
            "end_s": "1700",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.84722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "21.11111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.39",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1700",
            "end_s": "1710",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.11111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "21.375",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.71",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1710",
            "end_s": "1720",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.375",
            "battery_end_kwh": "21.63888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.03",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1720",
            "end_s": "1730",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.63888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "21.90277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.35",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1730",
            "end_s": "1740",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.90277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "22.16666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.67",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1740",
            "end_s": "1750",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.16666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "22.43055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.99",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1750",
            "end_s": "1760",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.43055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "22.69444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.31",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1760",
            "end_s": "1770",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.69444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "22.95833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.63",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1770",
            "end_s": "1780",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.95833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "23.22222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.95",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1780",
            "end_s": "1790",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "23.22222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "23.48611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "37.27",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1790",
            "end_s": "1800",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "23.48611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "23.75",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "37.59",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          }
        ],
        "events": [
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "utility",
            "value_kw": null,
            "sequence": 0,
            "origin": "scenario_event"
          },
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "generator",
            "value_kw": null,
            "sequence": 1,
            "origin": "scenario_event"
          },
          {
            "at_s": "607.8",
            "action": "battery_depleted",
            "target": "battery",
            "origin": "simulation"
          },
          {
            "at_s": "900",
            "action": "asset_up",
            "target": "utility",
            "value_kw": null,
            "sequence": 2,
            "origin": "scenario_event"
          },
          {
            "at_s": "900",
            "action": "asset_up",
            "target": "generator",
            "value_kw": null,
            "sequence": 3,
            "origin": "scenario_event"
          }
        ],
        "summary": {
          "requested_it_kwh": "500",
          "served_it_kwh": "418.8333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
          "unserved_it_kwh": "81.16666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
          "grid_kwh": "375.877192982456140350877192982456140350877192982456140350877192982456140350877192982456140350877193",
          "generator_kwh": "0",
          "distribution_loss_kwh": "22.04385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754385965",
          "battery_charge_loss_kwh": "1.25",
          "battery_discharge_loss_kwh": "10",
          "battery_stored_change_kwh": "-76.25",
          "unserved_duration_s": "292.2",
          "battery_final_kwh": "23.75",
          "peak_unserved_kw": "1000",
          "energy_balance_residual_kwh": "0",
          "grid_energy_charge": "37.59",
          "generator_energy_charge": "0.00",
          "total_incremental_energy_charge": "37.59",
          "cost_status": "illustrative",
          "service_status": "unserved_load",
          "interval_count": 181
        },
        "boundary": "Electrical supply, stored battery energy, conversion losses and served IT; cooling excluded",
        "limitations": [
          "No switching transient, protection study, cooling, workload queue or certification model.",
          "Generator starts on utility-asset unavailability only; downstream path faults do not request a start.",
          "Generator fuel is assumed sufficient for this horizon; its unit energy cost may be unknown.",
          "Initial stored battery energy is an opening balance; prior charging cost is excluded.",
          "Prices are illustrative inputs; costs exclude CAPEX and non-energy charges."
        ]
      }
    },
    {
      "configuration": "challenge",
      "input": "1",
      "result": "0",
      "unit": "s unserved",
      "calculation": {
        "schema_version": 2,
        "model": "single_load_electrical_continuity_v1",
        "engine_version": "2.0.1",
        "run_id": "a7f78458b94cca76c25a",
        "input_sha256": "171c46a72b66178b1e60fe68a869d7e9b191352e2f9b896933678cc5bf768df2",
        "mode": "SIMULATED",
        "quality": "synthetic_uncalibrated",
        "scenario": {
          "schema_version": 2,
          "id": "course-generator-failure",
          "name": "5. Add a failed generator",
          "currency": "USD",
          "duration_s": 1800,
          "step_s": 10,
          "it_demand_kw": "1000",
          "it_capacity_kw": "1000",
          "distribution_efficiency": "0.95",
          "tariff_per_kwh": "0.1",
          "generator_cost_per_kwh": null,
          "generator_start_delay_s": 30,
          "battery_capacity_kwh": "100",
          "battery_initial_kwh": "100",
          "battery_charge_kw": "100",
          "battery_charge_efficiency": "0.95",
          "battery_discharge_efficiency": "0.9",
          "source_ids": [
            "DEMO-ELECTRICAL-002",
            "EDU-POWER-001"
          ],
          "assets": [
            {
              "id": "utility",
              "name": "Utility feed",
              "kind": "utility",
              "capacity_kw": "1500",
              "failure_domains": [
                "utility-feed"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "generator",
              "name": "Standby generator",
              "kind": "generator",
              "capacity_kw": "1200",
              "failure_domains": [
                "generator-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "battery",
              "name": "UPS battery",
              "kind": "battery",
              "capacity_kw": "1200",
              "failure_domains": [
                "ups-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "main-bus",
              "name": "Main electrical bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "switchroom"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-a",
              "name": "Distribution A",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "a-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-b",
              "name": "Distribution B",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "b-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-bus",
              "name": "IT distribution bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "it-bus"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-load",
              "name": "Synthetic IT demand",
              "kind": "load",
              "capacity_kw": "2000",
              "failure_domains": [
                "it-hall"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            }
          ],
          "dependencies": [
            {
              "source": "utility",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "generator",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "battery",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-a",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-b",
              "relation": "feeds"
            },
            {
              "source": "path-a",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "path-b",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "it-bus",
              "target": "it-load",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "battery",
              "relation": "charges"
            }
          ],
          "events": [
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 900,
              "action": "asset_up",
              "target": "utility",
              "value_kw": null
            }
          ]
        },
        "intervals": [
          {
            "start_s": "0",
            "end_s": "10",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "10",
            "end_s": "20",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "20",
            "end_s": "30",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.88",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "30",
            "end_s": "40",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.17",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "40",
            "end_s": "50",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "50",
            "end_s": "60",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.75",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "60",
            "end_s": "70",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "70",
            "end_s": "80",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "80",
            "end_s": "90",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.63",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "90",
            "end_s": "100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.92",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "100",
            "end_s": "110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "110",
            "end_s": "120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.51",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "120",
            "end_s": "130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.80",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "130",
            "end_s": "140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "140",
            "end_s": "150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.39",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "150",
            "end_s": "160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.68",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "160",
            "end_s": "170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.97",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "170",
            "end_s": "180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.26",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "180",
            "end_s": "190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.56",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "190",
            "end_s": "200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.85",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "200",
            "end_s": "210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "210",
            "end_s": "220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.43",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "220",
            "end_s": "230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "230",
            "end_s": "240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "240",
            "end_s": "250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.31",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "250",
            "end_s": "260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.60",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "260",
            "end_s": "270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "270",
            "end_s": "280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.19",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "280",
            "end_s": "290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.48",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "290",
            "end_s": "300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "300",
            "end_s": "310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "96.7511371020142949967511371020142949967511371020142949967511371020142949967511371020142949967511371",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "starting",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "310",
            "end_s": "320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "96.7511371020142949967511371020142949967511371020142949967511371020142949967511371020142949967511371",
            "battery_end_kwh": "93.5022742040285899935022742040285899935022742040285899935022742040285899935022742040285899935022742",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "starting",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "320",
            "end_s": "330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "93.5022742040285899935022742040285899935022742040285899935022742040285899935022742040285899935022742",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "starting",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "330",
            "end_s": "340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "340",
            "end_s": "350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "350",
            "end_s": "360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "360",
            "end_s": "370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "370",
            "end_s": "380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "380",
            "end_s": "390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "390",
            "end_s": "400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "400",
            "end_s": "410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "410",
            "end_s": "420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "420",
            "end_s": "430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "430",
            "end_s": "440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "440",
            "end_s": "450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "450",
            "end_s": "460",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "460",
            "end_s": "470",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "470",
            "end_s": "480",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "480",
            "end_s": "490",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "490",
            "end_s": "500",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "500",
            "end_s": "510",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "510",
            "end_s": "520",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "520",
            "end_s": "530",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "530",
            "end_s": "540",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "540",
            "end_s": "550",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "550",
            "end_s": "560",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "560",
            "end_s": "570",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "570",
            "end_s": "580",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "580",
            "end_s": "590",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "590",
            "end_s": "600",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "600",
            "end_s": "610",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "610",
            "end_s": "620",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "620",
            "end_s": "630",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "630",
            "end_s": "640",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "640",
            "end_s": "650",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "650",
            "end_s": "660",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "660",
            "end_s": "670",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "670",
            "end_s": "680",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "680",
            "end_s": "690",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "690",
            "end_s": "700",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "700",
            "end_s": "710",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "710",
            "end_s": "720",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "720",
            "end_s": "730",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "730",
            "end_s": "740",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "740",
            "end_s": "750",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "750",
            "end_s": "760",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "760",
            "end_s": "770",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "770",
            "end_s": "780",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "780",
            "end_s": "790",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "790",
            "end_s": "800",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "800",
            "end_s": "810",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "810",
            "end_s": "820",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "820",
            "end_s": "830",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "830",
            "end_s": "840",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "840",
            "end_s": "850",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "850",
            "end_s": "860",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "860",
            "end_s": "870",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "870",
            "end_s": "880",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "880",
            "end_s": "890",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "890",
            "end_s": "900",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "running",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "900",
            "end_s": "910",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "90.51730019493177387914230019493177387914230019493177387914230019493177387914230019493177387914230019",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "910",
            "end_s": "920",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "90.51730019493177387914230019493177387914230019493177387914230019493177387914230019493177387914230019",
            "battery_end_kwh": "90.78118908382066276803118908382066276803118908382066276803118908382066276803118908382066276803118908",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.41",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "920",
            "end_s": "930",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "90.78118908382066276803118908382066276803118908382066276803118908382066276803118908382066276803118908",
            "battery_end_kwh": "91.04507797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "930",
            "end_s": "940",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "91.04507797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "battery_end_kwh": "91.30896686159844054580896686159844054580896686159844054580896686159844054580896686159844054580896686",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "940",
            "end_s": "950",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "91.30896686159844054580896686159844054580896686159844054580896686159844054580896686159844054580896686",
            "battery_end_kwh": "91.57285575048732943469785575048732943469785575048732943469785575048732943469785575048732943469785575",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.37",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "950",
            "end_s": "960",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "91.57285575048732943469785575048732943469785575048732943469785575048732943469785575048732943469785575",
            "battery_end_kwh": "91.83674463937621832358674463937621832358674463937621832358674463937621832358674463937621832358674464",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.69",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "960",
            "end_s": "970",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "91.83674463937621832358674463937621832358674463937621832358674463937621832358674463937621832358674464",
            "battery_end_kwh": "92.10063352826510721247563352826510721247563352826510721247563352826510721247563352826510721247563353",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.01",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "970",
            "end_s": "980",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "92.10063352826510721247563352826510721247563352826510721247563352826510721247563352826510721247563353",
            "battery_end_kwh": "92.36452241715399610136452241715399610136452241715399610136452241715399610136452241715399610136452242",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.33",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "980",
            "end_s": "990",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "92.36452241715399610136452241715399610136452241715399610136452241715399610136452241715399610136452242",
            "battery_end_kwh": "92.62841130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.65",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "990",
            "end_s": "1000",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "92.62841130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "92.89230019493177387914230019493177387914230019493177387914230019493177387914230019493177387914230019",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.97",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1000",
            "end_s": "1010",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "92.89230019493177387914230019493177387914230019493177387914230019493177387914230019493177387914230019",
            "battery_end_kwh": "93.15618908382066276803118908382066276803118908382066276803118908382066276803118908382066276803118908",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1010",
            "end_s": "1020",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "93.15618908382066276803118908382066276803118908382066276803118908382066276803118908382066276803118908",
            "battery_end_kwh": "93.42007797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1020",
            "end_s": "1030",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "93.42007797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "battery_end_kwh": "93.68396686159844054580896686159844054580896686159844054580896686159844054580896686159844054580896686",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.93",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1030",
            "end_s": "1040",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "93.68396686159844054580896686159844054580896686159844054580896686159844054580896686159844054580896686",
            "battery_end_kwh": "93.94785575048732943469785575048732943469785575048732943469785575048732943469785575048732943469785575",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1040",
            "end_s": "1050",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "93.94785575048732943469785575048732943469785575048732943469785575048732943469785575048732943469785575",
            "battery_end_kwh": "94.21174463937621832358674463937621832358674463937621832358674463937621832358674463937621832358674464",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1050",
            "end_s": "1060",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "94.21174463937621832358674463937621832358674463937621832358674463937621832358674463937621832358674464",
            "battery_end_kwh": "94.47563352826510721247563352826510721247563352826510721247563352826510721247563352826510721247563353",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1060",
            "end_s": "1070",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "94.47563352826510721247563352826510721247563352826510721247563352826510721247563352826510721247563353",
            "battery_end_kwh": "94.73952241715399610136452241715399610136452241715399610136452241715399610136452241715399610136452242",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.21",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1070",
            "end_s": "1080",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "94.73952241715399610136452241715399610136452241715399610136452241715399610136452241715399610136452242",
            "battery_end_kwh": "95.00341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1080",
            "end_s": "1090",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "95.00341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "95.26730019493177387914230019493177387914230019493177387914230019493177387914230019493177387914230019",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1090",
            "end_s": "1100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "95.26730019493177387914230019493177387914230019493177387914230019493177387914230019493177387914230019",
            "battery_end_kwh": "95.53118908382066276803118908382066276803118908382066276803118908382066276803118908382066276803118908",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1100",
            "end_s": "1110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "95.53118908382066276803118908382066276803118908382066276803118908382066276803118908382066276803118908",
            "battery_end_kwh": "95.79507797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1110",
            "end_s": "1120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "95.79507797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "battery_end_kwh": "96.05896686159844054580896686159844054580896686159844054580896686159844054580896686159844054580896686",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1120",
            "end_s": "1130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "96.05896686159844054580896686159844054580896686159844054580896686159844054580896686159844054580896686",
            "battery_end_kwh": "96.32285575048732943469785575048732943469785575048732943469785575048732943469785575048732943469785575",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1130",
            "end_s": "1140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "96.32285575048732943469785575048732943469785575048732943469785575048732943469785575048732943469785575",
            "battery_end_kwh": "96.58674463937621832358674463937621832358674463937621832358674463937621832358674463937621832358674464",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1140",
            "end_s": "1150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "96.58674463937621832358674463937621832358674463937621832358674463937621832358674463937621832358674464",
            "battery_end_kwh": "96.85063352826510721247563352826510721247563352826510721247563352826510721247563352826510721247563353",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.78",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1150",
            "end_s": "1160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "96.85063352826510721247563352826510721247563352826510721247563352826510721247563352826510721247563353",
            "battery_end_kwh": "97.11452241715399610136452241715399610136452241715399610136452241715399610136452241715399610136452242",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.10",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1160",
            "end_s": "1170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "97.11452241715399610136452241715399610136452241715399610136452241715399610136452241715399610136452242",
            "battery_end_kwh": "97.37841130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.42",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1170",
            "end_s": "1180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "97.37841130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "97.64230019493177387914230019493177387914230019493177387914230019493177387914230019493177387914230019",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.74",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1180",
            "end_s": "1190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "97.64230019493177387914230019493177387914230019493177387914230019493177387914230019493177387914230019",
            "battery_end_kwh": "97.90618908382066276803118908382066276803118908382066276803118908382066276803118908382066276803118908",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.06",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1190",
            "end_s": "1200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "97.90618908382066276803118908382066276803118908382066276803118908382066276803118908382066276803118908",
            "battery_end_kwh": "98.17007797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.38",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1200",
            "end_s": "1210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "98.17007797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "battery_end_kwh": "98.43396686159844054580896686159844054580896686159844054580896686159844054580896686159844054580896686",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1210",
            "end_s": "1220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "98.43396686159844054580896686159844054580896686159844054580896686159844054580896686159844054580896686",
            "battery_end_kwh": "98.69785575048732943469785575048732943469785575048732943469785575048732943469785575048732943469785575",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1220",
            "end_s": "1230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "98.69785575048732943469785575048732943469785575048732943469785575048732943469785575048732943469785575",
            "battery_end_kwh": "98.96174463937621832358674463937621832358674463937621832358674463937621832358674463937621832358674464",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1230",
            "end_s": "1240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "98.96174463937621832358674463937621832358674463937621832358674463937621832358674463937621832358674464",
            "battery_end_kwh": "99.22563352826510721247563352826510721247563352826510721247563352826510721247563352826510721247563353",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.66",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1240",
            "end_s": "1250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "99.22563352826510721247563352826510721247563352826510721247563352826510721247563352826510721247563353",
            "battery_end_kwh": "99.48952241715399610136452241715399610136452241715399610136452241715399610136452241715399610136452242",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.98",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1250",
            "end_s": "1260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "99.48952241715399610136452241715399610136452241715399610136452241715399610136452241715399610136452242",
            "battery_end_kwh": "99.75341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.30",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1260",
            "end_s": "1269.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "9.34441366574330563250230840258541089566020313942751615881809787626962142197599261311172668513388735",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "99.75341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.60",
            "energy": {
              "requested_it_kwh": "2.595670462706473786806196778495947471016723094285421155227249410074894839437775725864368523648302042",
              "served_it_kwh": "2.595670462706473786806196778495947471016723094285421155227249410074894839437775725864368523648302042",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.991851743856409259529247865740065769224538724465827542077724320033694578088804652443666877257779722",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1366142348792880940424314093945235511061433207518642713277499689513102547072513539928615012446474759",
              "battery_charge_loss_kwh": "0.01297835231353236893403098389247973735508361547142710577613624705037447419718887862932184261824151021",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.246588693957115009746588693957115009746588693957115009746588693957115009746588693957115009746588694",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1269.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1279.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1279.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1289.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1289.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1299.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.47",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1299.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1309.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1309.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1319.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.06",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1319.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1329.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.35",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1329.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1339.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.64",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1339.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1349.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.94",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1349.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1359.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.23",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1359.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1369.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.52",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1369.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1379.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.81",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1379.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1389.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.11",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1389.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1399.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.40",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1399.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1409.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.69",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1409.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1419.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.98",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1419.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1429.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.28",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1429.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1439.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1439.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1449.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1449.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1459.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.15",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1459.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1469.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.45",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1469.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1479.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.74",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1479.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1489.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.03",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1489.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1499.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.32",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1499.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1509.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1509.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1519.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.91",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1519.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1529.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.20",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1529.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1539.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.49",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1539.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1549.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.78",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1549.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1559.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.08",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1559.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1569.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.37",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1569.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1579.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.66",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1579.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1589.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.95",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1589.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1599.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1599.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1609.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1609.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1619.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.83",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1619.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1629.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.12",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1629.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1639.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.42",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1639.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1649.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.71",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1649.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1659.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.00",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1659.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1669.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1669.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1679.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.59",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1679.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1689.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.88",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1689.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1699.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.17",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1699.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1709.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1709.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1719.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.76",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1719.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1729.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1729.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1739.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1739.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1749.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.63",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1749.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1759.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.92",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1759.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1769.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1769.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1779.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.51",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1779.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1789.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.80",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1789.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1799.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1799.344413665743305632502308402585410895660203139427516158818097876269621421975992613111726685133887",
            "end_s": "1800",
            "duration_s": "0.65558633425669436749769159741458910433979686057248384118190212373037857802400738688827331486611265",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.11",
            "energy": {
              "requested_it_kwh": "0.1821073150713039909715809992818303067610546834923566225505283677028829383400020519134092541294757361",
              "served_it_kwh": "0.1821073150713039909715809992818303067610546834923566225505283677028829383400020519134092541294757361",
              "unserved_it_kwh": "0",
              "grid_kwh": "0.1916919106013726220753484202966634808011101931498490763689772291609294087789495283299044780310270907",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.009584595530068631103767421014833174040055509657492453818448861458046470438947476416495223901551354533",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          }
        ],
        "events": [
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "utility",
            "value_kw": null,
            "sequence": 0,
            "origin": "scenario_event"
          },
          {
            "at_s": "300",
            "action": "generator_start_requested",
            "target": "generator",
            "ready_at_s": "330",
            "origin": "simulation"
          },
          {
            "at_s": "900",
            "action": "asset_up",
            "target": "utility",
            "value_kw": null,
            "sequence": 1,
            "origin": "scenario_event"
          }
        ],
        "summary": {
          "requested_it_kwh": "500",
          "served_it_kwh": "500",
          "unserved_it_kwh": "0",
          "grid_kwh": "361.1367600287267877295578126603057350979788652918846824663999179234636298348209705550425772032420232",
          "generator_kwh": "166.6666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
          "distribution_loss_kwh": "26.31578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631578947",
          "battery_charge_loss_kwh": "0.5129783523135323689340309838924797373550836154714271057761362470503744741971888786293218426182415102",
          "battery_discharge_loss_kwh": "0.9746588693957115009746588693957115009746588693957115009746588693957115009746588693957115009746588694",
          "battery_stored_change_kwh": "0",
          "unserved_duration_s": "0",
          "battery_final_kwh": "100",
          "peak_unserved_kw": "0",
          "energy_balance_residual_kwh": "0",
          "grid_energy_charge": "36.11",
          "generator_energy_charge": null,
          "total_incremental_energy_charge": null,
          "cost_status": "unknown_component",
          "service_status": "served_throughout",
          "interval_count": 181
        },
        "boundary": "Electrical supply, stored battery energy, conversion losses and served IT; cooling excluded",
        "limitations": [
          "No switching transient, protection study, cooling, workload queue or certification model.",
          "Generator starts on utility-asset unavailability only; downstream path faults do not request a start.",
          "Generator fuel is assumed sufficient for this horizon; its unit energy cost may be unknown.",
          "Initial stored battery energy is an opening balance; prior charging cost is excluded.",
          "Prices are illustrative inputs; costs exclude CAPEX and non-energy charges."
        ]
      }
    }
  ]
}