  "schema_version": 1,
  "lesson_id": "recovery-deadline",
  "lesson_url": "https://khanlab.co.technology/learn/recovery-deadline/",
  "engine_version": "2.0.1",
  "source_revision": "4878472c4d6c166c3dbd81aee292a0a56e89ffff",
  "result_unit": "s unserved",
  "records": [
    {
      "configuration": "starting",
      "input": "57",
      "result": "0.1865",
      "unit": "s unserved",
      "calculation": {
        "schema_version": 2,
        "model": "single_load_electrical_continuity_v1",
        "engine_version": "2.0.1",
        "run_id": "6b8f4034f2fc0eecdcf5",
        "input_sha256": "8d11474d47b32dd53163a47d676169f63fa1ed40440307e3cd6008b2edf8e269",
        "mode": "SIMULATED",
        "quality": "synthetic_uncalibrated",
        "scenario": {
          "schema_version": 2,
          "id": "course-recovery-deadline",
          "name": "11. Catch a sub-second service gap",
          "currency": "USD",
          "duration_s": 1800,
          "step_s": 10,
          "it_demand_kw": "1000",
          "it_capacity_kw": "1000",
          "distribution_efficiency": "0.95",
          "tariff_per_kwh": "0.1",
          "generator_cost_per_kwh": null,
          "generator_start_delay_s": 30,
          "battery_capacity_kwh": "100",
          "battery_initial_kwh": "57",
          "battery_charge_kw": "100",
          "battery_charge_efficiency": "0.95",
          "battery_discharge_efficiency": "0.9",
          "source_ids": [
            "DEMO-ELECTRICAL-002",
            "EDU-POWER-001"
          ],
          "assets": [
            {
              "id": "utility",
              "name": "Utility feed",
              "kind": "utility",
              "capacity_kw": "1500",
              "failure_domains": [
                "utility-feed"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "generator",
              "name": "Standby generator",
              "kind": "generator",
              "capacity_kw": "1200",
              "failure_domains": [
                "generator-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "battery",
              "name": "UPS battery",
              "kind": "battery",
              "capacity_kw": "1200",
              "failure_domains": [
                "ups-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "main-bus",
              "name": "Main electrical bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "switchroom"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-a",
              "name": "Distribution A",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "a-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-b",
              "name": "Distribution B",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "b-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-bus",
              "name": "IT distribution bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "it-bus"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-load",
              "name": "Synthetic IT demand",
              "kind": "load",
              "capacity_kw": "2000",
              "failure_domains": [
                "it-hall"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            }
          ],
          "dependencies": [
            {
              "source": "utility",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "generator",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "battery",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-a",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-b",
              "relation": "feeds"
            },
            {
              "source": "path-a",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "path-b",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "it-bus",
              "target": "it-load",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "battery",
              "relation": "charges"
            }
          ],
          "events": [
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "generator",
              "value_kw": null
            },
            {
              "at_s": 500,
              "action": "asset_up",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 900,
              "action": "asset_up",
              "target": "generator",
              "value_kw": null
            }
          ]
        },
        "intervals": [
          {
            "start_s": "0",
            "end_s": "10",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "57",
            "battery_end_kwh": "57.26388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.32",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "10",
            "end_s": "20",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "57.26388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "57.52777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.64",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "20",
            "end_s": "30",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "57.52777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "57.79166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.96",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "30",
            "end_s": "40",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "57.79166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "58.05555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.28",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "40",
            "end_s": "50",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "58.05555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "58.31944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.60",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "50",
            "end_s": "60",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "58.31944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "58.58333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.92",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "60",
            "end_s": "70",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "58.58333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "58.84722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.24",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "70",
            "end_s": "80",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "58.84722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "59.11111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.56",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "80",
            "end_s": "90",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "59.11111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "59.375",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.88",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "90",
            "end_s": "100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "59.375",
            "battery_end_kwh": "59.63888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.20",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "100",
            "end_s": "110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "59.63888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "59.90277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.52",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "110",
            "end_s": "120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "59.90277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "60.16666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.84",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "120",
            "end_s": "130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "60.16666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "60.43055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.16",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "130",
            "end_s": "140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "60.43055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "60.69444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.48",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "140",
            "end_s": "150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "60.69444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "60.95833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.80",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "150",
            "end_s": "160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "60.95833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "61.22222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.12",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "160",
            "end_s": "170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "61.22222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "61.48611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.44",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "170",
            "end_s": "180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "61.48611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "61.75",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.76",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "180",
            "end_s": "190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "61.75",
            "battery_end_kwh": "62.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.08",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "190",
            "end_s": "200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "62.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "62.27777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.40",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "200",
            "end_s": "210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "62.27777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "62.54166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.72",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "210",
            "end_s": "220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "62.54166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "62.80555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.04",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "220",
            "end_s": "230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "62.80555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "63.06944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.36",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "230",
            "end_s": "240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "63.06944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "63.33333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.68",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "240",
            "end_s": "250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "63.33333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "63.59722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.00",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "250",
            "end_s": "260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "63.59722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "63.86111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.32",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "260",
            "end_s": "270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "63.86111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "64.125",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.64",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "270",
            "end_s": "280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "64.125",
            "battery_end_kwh": "64.38888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.96",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "280",
            "end_s": "290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "64.38888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "64.65277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "290",
            "end_s": "300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "64.65277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "64.91666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "300",
            "end_s": "310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "64.91666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "61.66780376868096166341780376868096166341780376868096166341780376868096166341780376868096166341780377",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "310",
            "end_s": "320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "61.66780376868096166341780376868096166341780376868096166341780376868096166341780376868096166341780377",
            "battery_end_kwh": "58.41894087069525666016894087069525666016894087069525666016894087069525666016894087069525666016894087",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "320",
            "end_s": "330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "58.41894087069525666016894087069525666016894087069525666016894087069525666016894087069525666016894087",
            "battery_end_kwh": "55.17007797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "330",
            "end_s": "340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "55.17007797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "battery_end_kwh": "51.92121507472384665367121507472384665367121507472384665367121507472384665367121507472384665367121507",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "340",
            "end_s": "350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "51.92121507472384665367121507472384665367121507472384665367121507472384665367121507472384665367121507",
            "battery_end_kwh": "48.67235217673814165042235217673814165042235217673814165042235217673814165042235217673814165042235218",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "350",
            "end_s": "360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "48.67235217673814165042235217673814165042235217673814165042235217673814165042235217673814165042235218",
            "battery_end_kwh": "45.42348927875243664717348927875243664717348927875243664717348927875243664717348927875243664717348928",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "360",
            "end_s": "370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "45.42348927875243664717348927875243664717348927875243664717348927875243664717348927875243664717348928",
            "battery_end_kwh": "42.17462638076673164392462638076673164392462638076673164392462638076673164392462638076673164392462638",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "370",
            "end_s": "380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "42.17462638076673164392462638076673164392462638076673164392462638076673164392462638076673164392462638",
            "battery_end_kwh": "38.92576348278102664067576348278102664067576348278102664067576348278102664067576348278102664067576348",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "380",
            "end_s": "390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "38.92576348278102664067576348278102664067576348278102664067576348278102664067576348278102664067576348",
            "battery_end_kwh": "35.67690058479532163742690058479532163742690058479532163742690058479532163742690058479532163742690058",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "390",
            "end_s": "400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "35.67690058479532163742690058479532163742690058479532163742690058479532163742690058479532163742690058",
            "battery_end_kwh": "32.42803768680961663417803768680961663417803768680961663417803768680961663417803768680961663417803769",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "400",
            "end_s": "410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "32.42803768680961663417803768680961663417803768680961663417803768680961663417803768680961663417803769",
            "battery_end_kwh": "29.17917478882391163092917478882391163092917478882391163092917478882391163092917478882391163092917479",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "410",
            "end_s": "420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "29.17917478882391163092917478882391163092917478882391163092917478882391163092917478882391163092917479",
            "battery_end_kwh": "25.93031189083820662768031189083820662768031189083820662768031189083820662768031189083820662768031189",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "420",
            "end_s": "430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "25.93031189083820662768031189083820662768031189083820662768031189083820662768031189083820662768031189",
            "battery_end_kwh": "22.68144899285250162443144899285250162443144899285250162443144899285250162443144899285250162443144899",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "430",
            "end_s": "440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "22.68144899285250162443144899285250162443144899285250162443144899285250162443144899285250162443144899",
            "battery_end_kwh": "19.43258609486679662118258609486679662118258609486679662118258609486679662118258609486679662118258609",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "440",
            "end_s": "450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "19.43258609486679662118258609486679662118258609486679662118258609486679662118258609486679662118258609",
            "battery_end_kwh": "16.1837231968810916179337231968810916179337231968810916179337231968810916179337231968810916179337232",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "450",
            "end_s": "460",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "16.1837231968810916179337231968810916179337231968810916179337231968810916179337231968810916179337232",
            "battery_end_kwh": "12.9348602988953866146848602988953866146848602988953866146848602988953866146848602988953866146848603",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "460",
            "end_s": "470",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "12.9348602988953866146848602988953866146848602988953866146848602988953866146848602988953866146848603",
            "battery_end_kwh": "9.685997400909681611435997400909681611435997400909681611435997400909681611435997400909681611435997401",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "470",
            "end_s": "480",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "9.685997400909681611435997400909681611435997400909681611435997400909681611435997400909681611435997401",
            "battery_end_kwh": "6.437134502923976608187134502923976608187134502923976608187134502923976608187134502923976608187134503",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "480",
            "end_s": "490",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "6.437134502923976608187134502923976608187134502923976608187134502923976608187134502923976608187134503",
            "battery_end_kwh": "3.188271604938271604938271604938271604938271604938271604938271604938271604938271604938271604938271605",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "490",
            "end_s": "499.8135",
            "duration_s": "9.8135",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "3.188271604938271604938271604938271604938271604938271604938271604938271604938271604938271604938271605",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.725972222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
              "served_it_kwh": "2.725972222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1434722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3188271604938271604938271604938271604938271604938271604938271604938271604938271604938271604938271605",
              "battery_stored_change_kwh": "-3.188271604938271604938271604938271604938271604938271604938271604938271604938271604938271604938271605",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "499.8135",
            "end_s": "500",
            "duration_s": "0.1865",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "0.05180555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
              "served_it_kwh": "0",
              "unserved_it_kwh": "0.05180555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0.1865"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "500",
            "end_s": "510",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.93",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "510",
            "end_s": "520",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "0.5277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "520",
            "end_s": "530",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "0.5277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "0.7916666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "530",
            "end_s": "540",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "0.7916666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "1.055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "540",
            "end_s": "550",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "1.319444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.21",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "550",
            "end_s": "560",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.319444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "1.583333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.53",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "560",
            "end_s": "570",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.583333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.85",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "570",
            "end_s": "580",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.847222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "2.111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.17",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "580",
            "end_s": "590",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "2.375",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.49",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "590",
            "end_s": "600",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.375",
            "battery_end_kwh": "2.638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.81",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "600",
            "end_s": "610",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "2.902777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.13",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "610",
            "end_s": "620",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.902777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "3.166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.45",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "620",
            "end_s": "630",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "3.430555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "630",
            "end_s": "640",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.430555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "3.694444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "640",
            "end_s": "650",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.694444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "3.958333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.41",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "650",
            "end_s": "660",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.958333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "4.222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "660",
            "end_s": "670",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "4.222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "4.486111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "670",
            "end_s": "680",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "4.486111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "4.75",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.37",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "680",
            "end_s": "690",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "4.75",
            "battery_end_kwh": "5.013888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.69",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "690",
            "end_s": "700",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.013888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "5.277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.01",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "700",
            "end_s": "710",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "5.541666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.33",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "710",
            "end_s": "720",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.541666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "5.805555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.65",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "720",
            "end_s": "730",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.805555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "6.069444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.97",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "730",
            "end_s": "740",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.069444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "6.333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "740",
            "end_s": "750",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "6.597222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "750",
            "end_s": "760",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.597222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "6.861111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.93",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "760",
            "end_s": "770",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.861111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "7.125",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "770",
            "end_s": "780",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.125",
            "battery_end_kwh": "7.388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "780",
            "end_s": "790",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "7.652777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "790",
            "end_s": "800",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.652777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "7.916666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.21",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "800",
            "end_s": "810",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.916666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "8.180555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.53",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "810",
            "end_s": "820",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.180555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "8.444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.85",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "820",
            "end_s": "830",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "8.708333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.17",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "830",
            "end_s": "840",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.708333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "8.972222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.49",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "840",
            "end_s": "850",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.972222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "9.236111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.81",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "850",
            "end_s": "860",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "9.236111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "9.5",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.13",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "860",
            "end_s": "870",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "9.5",
            "battery_end_kwh": "9.763888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.45",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "870",
            "end_s": "880",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "9.763888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "10.02777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "880",
            "end_s": "890",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.02777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "10.29166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "890",
            "end_s": "900",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.29166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "10.55555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.41",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "900",
            "end_s": "910",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.55555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "10.81944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "910",
            "end_s": "920",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.81944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "11.08333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "920",
            "end_s": "930",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.08333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "11.34722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.37",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "930",
            "end_s": "940",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.34722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "11.61111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.69",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "940",
            "end_s": "950",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.61111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "11.875",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.01",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "950",
            "end_s": "960",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.875",
            "battery_end_kwh": "12.13888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.33",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "960",
            "end_s": "970",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.13888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "12.40277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.65",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "970",
            "end_s": "980",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.40277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "12.66666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.97",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "980",
            "end_s": "990",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.66666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "12.93055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "990",
            "end_s": "1000",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.93055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "13.19444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1000",
            "end_s": "1010",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.19444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "13.45833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.93",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1010",
            "end_s": "1020",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.45833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "13.72222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1020",
            "end_s": "1030",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.72222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "13.98611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1030",
            "end_s": "1040",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.98611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "14.25",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1040",
            "end_s": "1050",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "14.25",
            "battery_end_kwh": "14.51388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.21",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1050",
            "end_s": "1060",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "14.51388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "14.77777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1060",
            "end_s": "1070",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "14.77777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "15.04166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1070",
            "end_s": "1080",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.04166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "15.30555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1080",
            "end_s": "1090",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.30555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "15.56944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1090",
            "end_s": "1100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.56944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "15.83333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1100",
            "end_s": "1110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.83333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "16.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1110",
            "end_s": "1120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.09722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "16.36111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1120",
            "end_s": "1130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.36111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "16.625",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.78",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1130",
            "end_s": "1140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.625",
            "battery_end_kwh": "16.88888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.10",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1140",
            "end_s": "1150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.88888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "17.15277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.42",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1150",
            "end_s": "1160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.15277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "17.41666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.74",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1160",
            "end_s": "1170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.41666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "17.68055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.06",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1170",
            "end_s": "1180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.68055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "17.94444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.38",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1180",
            "end_s": "1190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.94444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "18.20833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1190",
            "end_s": "1200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "18.20833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "18.47222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1200",
            "end_s": "1210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "18.47222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "18.73611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1210",
            "end_s": "1220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "18.73611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "19",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.66",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1220",
            "end_s": "1230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19",
            "battery_end_kwh": "19.26388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.98",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1230",
            "end_s": "1240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19.26388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "19.52777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.30",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1240",
            "end_s": "1250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19.52777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "19.79166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.62",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1250",
            "end_s": "1260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19.79166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "20.05555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.94",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1260",
            "end_s": "1270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.05555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "20.31944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.26",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1270",
            "end_s": "1280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.31944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "20.58333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1280",
            "end_s": "1290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.58333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "20.84722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.90",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1290",
            "end_s": "1300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.84722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "21.11111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1300",
            "end_s": "1310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.11111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "21.375",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1310",
            "end_s": "1320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.375",
            "battery_end_kwh": "21.63888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1320",
            "end_s": "1330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.63888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "21.90277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1330",
            "end_s": "1340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.90277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "22.16666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1340",
            "end_s": "1350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.16666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "22.43055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1350",
            "end_s": "1360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.43055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "22.69444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "37.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1360",
            "end_s": "1370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.69444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "22.95833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "37.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1370",
            "end_s": "1380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.95833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "23.22222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "37.78",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1380",
            "end_s": "1390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "23.22222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "23.48611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "38.10",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1390",
            "end_s": "1400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "23.48611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "23.75",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "38.42",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1400",
            "end_s": "1410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "23.75",
            "battery_end_kwh": "24.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "38.74",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1410",
            "end_s": "1420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "24.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "24.27777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "39.06",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1420",
            "end_s": "1430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "24.27777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "24.54166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "39.38",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1430",
            "end_s": "1440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "24.54166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "24.80555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "39.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1440",
            "end_s": "1450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "24.80555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "25.06944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "40.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1450",
            "end_s": "1460",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "25.06944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "25.33333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "40.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1460",
            "end_s": "1470",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "25.33333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "25.59722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "40.66",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1470",
            "end_s": "1480",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "25.59722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "25.86111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "40.98",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1480",
            "end_s": "1490",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "25.86111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "26.125",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "41.30",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1490",
            "end_s": "1500",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "26.125",
            "battery_end_kwh": "26.38888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "41.62",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1500",
            "end_s": "1510",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "26.38888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "26.65277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "41.94",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1510",
            "end_s": "1520",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "26.65277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "26.91666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "42.26",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1520",
            "end_s": "1530",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "26.91666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "27.18055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "42.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1530",
            "end_s": "1540",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "27.18055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "27.44444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "42.90",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1540",
            "end_s": "1550",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "27.44444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "27.70833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "43.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1550",
            "end_s": "1560",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "27.70833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "27.97222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "43.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1560",
            "end_s": "1570",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "27.97222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "28.23611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "43.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1570",
            "end_s": "1580",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "28.23611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "28.5",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "44.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1580",
            "end_s": "1590",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "28.5",
            "battery_end_kwh": "28.76388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "44.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1590",
            "end_s": "1600",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "28.76388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "29.02777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "44.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1600",
            "end_s": "1610",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "29.02777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "29.29166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "45.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1610",
            "end_s": "1620",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "29.29166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "29.55555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "45.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1620",
            "end_s": "1630",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "29.55555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "29.81944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "45.79",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1630",
            "end_s": "1640",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "29.81944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "30.08333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "46.11",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1640",
            "end_s": "1650",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "30.08333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "30.34722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "46.43",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1650",
            "end_s": "1660",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "30.34722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "30.61111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "46.75",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1660",
            "end_s": "1670",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "30.61111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "30.875",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "47.07",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1670",
            "end_s": "1680",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "30.875",
            "battery_end_kwh": "31.13888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "47.39",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1680",
            "end_s": "1690",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "31.13888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "31.40277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "47.71",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1690",
            "end_s": "1700",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "31.40277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "31.66666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "48.03",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1700",
            "end_s": "1710",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "31.66666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "31.93055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "48.35",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1710",
            "end_s": "1720",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "31.93055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "32.19444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "48.67",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1720",
            "end_s": "1730",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "32.19444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "32.45833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "48.99",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1730",
            "end_s": "1740",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "32.45833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "32.72222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "49.31",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1740",
            "end_s": "1750",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "32.72222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "32.98611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "49.63",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1750",
            "end_s": "1760",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "32.98611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "33.25",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "49.95",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1760",
            "end_s": "1770",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "33.25",
            "battery_end_kwh": "33.51388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "50.27",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1770",
            "end_s": "1780",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "33.51388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "33.77777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "50.59",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1780",
            "end_s": "1790",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "33.77777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "34.04166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "50.91",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1790",
            "end_s": "1800",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "34.04166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "34.30555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "51.23",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          }
        ],
        "events": [
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "utility",
            "value_kw": null,
            "sequence": 0,
            "origin": "scenario_event"
          },
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "generator",
            "value_kw": null,
            "sequence": 1,
            "origin": "scenario_event"
          },
          {
            "at_s": "499.8135",
            "action": "battery_depleted",
            "target": "battery",
            "origin": "simulation"
          },
          {
            "at_s": "500",
            "action": "asset_up",
            "target": "utility",
            "value_kw": null,
            "sequence": 2,
            "origin": "scenario_event"
          },
          {
            "at_s": "900",
            "action": "asset_up",
            "target": "generator",
            "value_kw": null,
            "sequence": 3,
            "origin": "scenario_event"
          }
        ],
        "summary": {
          "requested_it_kwh": "500",
          "served_it_kwh": "499.9481944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
          "unserved_it_kwh": "0.05180555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
          "grid_kwh": "512.2807017543859649122807017543859649122807017543859649122807017543859649122807017543859649122807018",
          "generator_kwh": "0",
          "distribution_loss_kwh": "26.31306286549707602339181286549707602339181286549707602339181286549707602339181286549707602339181287",
          "battery_charge_loss_kwh": "2.222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
          "battery_discharge_loss_kwh": "6.491666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
          "battery_stored_change_kwh": "-22.69444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
          "unserved_duration_s": "0.1865",
          "battery_final_kwh": "34.30555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
          "peak_unserved_kw": "1000",
          "energy_balance_residual_kwh": "0",
          "grid_energy_charge": "51.23",
          "generator_energy_charge": "0.00",
          "total_incremental_energy_charge": "51.23",
          "cost_status": "illustrative",
          "service_status": "unserved_load",
          "interval_count": 181
        },
        "boundary": "Electrical supply, stored battery energy, conversion losses and served IT; cooling excluded",
        "limitations": [
          "No switching transient, protection study, cooling, workload queue or certification model.",
          "Generator starts on utility-asset unavailability only; downstream path faults do not request a start.",
          "Generator fuel is assumed sufficient for this horizon; its unit energy cost may be unknown.",
          "Initial stored battery energy is an opening balance; prior charging cost is excluded.",
          "Prices are illustrative inputs; costs exclude CAPEX and non-energy charges."
        ]
      }
    },
    {
      "configuration": "challenge",
      "input": "58",
      "result": "0",
      "unit": "s unserved",
      "calculation": {
        "schema_version": 2,
        "model": "single_load_electrical_continuity_v1",
        "engine_version": "2.0.1",
        "run_id": "62caa2015618381816c7",
        "input_sha256": "84880d57459f436c21803c31017c2151e55573499a298469a8389c78d543362b",
        "mode": "SIMULATED",
        "quality": "synthetic_uncalibrated",
        "scenario": {
          "schema_version": 2,
          "id": "course-recovery-deadline",
          "name": "11. Catch a sub-second service gap",
          "currency": "USD",
          "duration_s": 1800,
          "step_s": 10,
          "it_demand_kw": "1000",
          "it_capacity_kw": "1000",
          "distribution_efficiency": "0.95",
          "tariff_per_kwh": "0.1",
          "generator_cost_per_kwh": null,
          "generator_start_delay_s": 30,
          "battery_capacity_kwh": "100",
          "battery_initial_kwh": "58",
          "battery_charge_kw": "100",
          "battery_charge_efficiency": "0.95",
          "battery_discharge_efficiency": "0.9",
          "source_ids": [
            "DEMO-ELECTRICAL-002",
            "EDU-POWER-001"
          ],
          "assets": [
            {
              "id": "utility",
              "name": "Utility feed",
              "kind": "utility",
              "capacity_kw": "1500",
              "failure_domains": [
                "utility-feed"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "generator",
              "name": "Standby generator",
              "kind": "generator",
              "capacity_kw": "1200",
              "failure_domains": [
                "generator-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "battery",
              "name": "UPS battery",
              "kind": "battery",
              "capacity_kw": "1200",
              "failure_domains": [
                "ups-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "main-bus",
              "name": "Main electrical bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "switchroom"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-a",
              "name": "Distribution A",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "a-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-b",
              "name": "Distribution B",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "b-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-bus",
              "name": "IT distribution bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "it-bus"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-load",
              "name": "Synthetic IT demand",
              "kind": "load",
              "capacity_kw": "2000",
              "failure_domains": [
                "it-hall"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            }
          ],
          "dependencies": [
            {
              "source": "utility",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "generator",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "battery",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-a",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-b",
              "relation": "feeds"
            },
            {
              "source": "path-a",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "path-b",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "it-bus",
              "target": "it-load",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "battery",
              "relation": "charges"
            }
          ],
          "events": [
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "generator",
              "value_kw": null
            },
            {
              "at_s": 500,
              "action": "asset_up",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 900,
              "action": "asset_up",
              "target": "generator",
              "value_kw": null
            }
          ]
        },
        "intervals": [
          {
            "start_s": "0",
            "end_s": "10",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "58",
            "battery_end_kwh": "58.26388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.32",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "10",
            "end_s": "20",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "58.26388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "58.52777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.64",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "20",
            "end_s": "30",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "58.52777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "58.79166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.96",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "30",
            "end_s": "40",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "58.79166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "59.05555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.28",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "40",
            "end_s": "50",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "59.05555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "59.31944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.60",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "50",
            "end_s": "60",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "59.31944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "59.58333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.92",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "60",
            "end_s": "70",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "59.58333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "59.84722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.24",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "70",
            "end_s": "80",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "59.84722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "60.11111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.56",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "80",
            "end_s": "90",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "60.11111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "60.375",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.88",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "90",
            "end_s": "100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "60.375",
            "battery_end_kwh": "60.63888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.20",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "100",
            "end_s": "110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "60.63888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "60.90277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.52",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "110",
            "end_s": "120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "60.90277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "61.16666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.84",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "120",
            "end_s": "130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "61.16666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "61.43055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.16",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "130",
            "end_s": "140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "61.43055555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "61.69444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.48",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "140",
            "end_s": "150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "61.69444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "61.95833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.80",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "150",
            "end_s": "160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "61.95833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "62.22222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.12",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "160",
            "end_s": "170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "62.22222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "62.48611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.44",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "170",
            "end_s": "180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "62.48611111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "62.75",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.76",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "180",
            "end_s": "190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "62.75",
            "battery_end_kwh": "63.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.08",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "190",
            "end_s": "200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "63.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "63.27777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.40",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "200",
            "end_s": "210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "63.27777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "63.54166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.72",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "210",
            "end_s": "220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "63.54166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "63.80555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.04",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "220",
            "end_s": "230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "63.80555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555555556",
            "battery_end_kwh": "64.06944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.36",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "230",
            "end_s": "240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "64.06944444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
            "battery_end_kwh": "64.33333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.68",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "240",
            "end_s": "250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "64.33333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
            "battery_end_kwh": "64.59722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.00",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "250",
            "end_s": "260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "64.59722222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
            "battery_end_kwh": "64.86111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.32",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "260",
            "end_s": "270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "64.86111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
            "battery_end_kwh": "65.125",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.64",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "270",
            "end_s": "280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "65.125",
            "battery_end_kwh": "65.38888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.96",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "280",
            "end_s": "290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "65.38888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
            "battery_end_kwh": "65.65277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "290",
            "end_s": "300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "65.65277777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
            "battery_end_kwh": "65.91666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "300",
            "end_s": "310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "65.91666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
            "battery_end_kwh": "62.66780376868096166341780376868096166341780376868096166341780376868096166341780376868096166341780377",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "310",
            "end_s": "320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "62.66780376868096166341780376868096166341780376868096166341780376868096166341780376868096166341780377",
            "battery_end_kwh": "59.41894087069525666016894087069525666016894087069525666016894087069525666016894087069525666016894087",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "320",
            "end_s": "330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "59.41894087069525666016894087069525666016894087069525666016894087069525666016894087069525666016894087",
            "battery_end_kwh": "56.17007797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "330",
            "end_s": "340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "56.17007797270955165692007797270955165692007797270955165692007797270955165692007797270955165692007797",
            "battery_end_kwh": "52.92121507472384665367121507472384665367121507472384665367121507472384665367121507472384665367121507",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "340",
            "end_s": "350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "52.92121507472384665367121507472384665367121507472384665367121507472384665367121507472384665367121507",
            "battery_end_kwh": "49.67235217673814165042235217673814165042235217673814165042235217673814165042235217673814165042235218",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "350",
            "end_s": "360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "49.67235217673814165042235217673814165042235217673814165042235217673814165042235217673814165042235218",
            "battery_end_kwh": "46.42348927875243664717348927875243664717348927875243664717348927875243664717348927875243664717348928",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "360",
            "end_s": "370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "46.42348927875243664717348927875243664717348927875243664717348927875243664717348927875243664717348928",
            "battery_end_kwh": "43.17462638076673164392462638076673164392462638076673164392462638076673164392462638076673164392462638",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "370",
            "end_s": "380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "43.17462638076673164392462638076673164392462638076673164392462638076673164392462638076673164392462638",
            "battery_end_kwh": "39.92576348278102664067576348278102664067576348278102664067576348278102664067576348278102664067576348",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "380",
            "end_s": "390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "39.92576348278102664067576348278102664067576348278102664067576348278102664067576348278102664067576348",
            "battery_end_kwh": "36.67690058479532163742690058479532163742690058479532163742690058479532163742690058479532163742690058",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "390",
            "end_s": "400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "36.67690058479532163742690058479532163742690058479532163742690058479532163742690058479532163742690058",
            "battery_end_kwh": "33.42803768680961663417803768680961663417803768680961663417803768680961663417803768680961663417803769",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "400",
            "end_s": "410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "33.42803768680961663417803768680961663417803768680961663417803768680961663417803768680961663417803769",
            "battery_end_kwh": "30.17917478882391163092917478882391163092917478882391163092917478882391163092917478882391163092917479",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "410",
            "end_s": "420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "30.17917478882391163092917478882391163092917478882391163092917478882391163092917478882391163092917479",
            "battery_end_kwh": "26.93031189083820662768031189083820662768031189083820662768031189083820662768031189083820662768031189",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "420",
            "end_s": "430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "26.93031189083820662768031189083820662768031189083820662768031189083820662768031189083820662768031189",
            "battery_end_kwh": "23.68144899285250162443144899285250162443144899285250162443144899285250162443144899285250162443144899",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "430",
            "end_s": "440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "23.68144899285250162443144899285250162443144899285250162443144899285250162443144899285250162443144899",
            "battery_end_kwh": "20.43258609486679662118258609486679662118258609486679662118258609486679662118258609486679662118258609",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "440",
            "end_s": "450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "20.43258609486679662118258609486679662118258609486679662118258609486679662118258609486679662118258609",
            "battery_end_kwh": "17.1837231968810916179337231968810916179337231968810916179337231968810916179337231968810916179337232",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "450",
            "end_s": "460",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "17.1837231968810916179337231968810916179337231968810916179337231968810916179337231968810916179337232",
            "battery_end_kwh": "13.9348602988953866146848602988953866146848602988953866146848602988953866146848602988953866146848603",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "460",
            "end_s": "470",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "13.9348602988953866146848602988953866146848602988953866146848602988953866146848602988953866146848603",
            "battery_end_kwh": "10.6859974009096816114359974009096816114359974009096816114359974009096816114359974009096816114359974",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "470",
            "end_s": "480",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "10.6859974009096816114359974009096816114359974009096816114359974009096816114359974009096816114359974",
            "battery_end_kwh": "7.437134502923976608187134502923976608187134502923976608187134502923976608187134502923976608187134503",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "480",
            "end_s": "490",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "7.437134502923976608187134502923976608187134502923976608187134502923976608187134502923976608187134503",
            "battery_end_kwh": "4.188271604938271604938271604938271604938271604938271604938271604938271604938271604938271604938271605",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "490",
            "end_s": "500",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "4.188271604938271604938271604938271604938271604938271604938271604938271604938271604938271604938271605",
            "battery_end_kwh": "0.939408706952566601689408706952566601689408706952566601689408706952566601689408706952566601689408707",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "500",
            "end_s": "510",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "0.939408706952566601689408706952566601689408706952566601689408706952566601689408706952566601689408707",
            "battery_end_kwh": "1.203297595841455490578297595841455490578297595841455490578297595841455490578297595841455490578297596",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.93",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "510",
            "end_s": "520",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.203297595841455490578297595841455490578297595841455490578297595841455490578297595841455490578297596",
            "battery_end_kwh": "1.467186484730344379467186484730344379467186484730344379467186484730344379467186484730344379467186485",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "520",
            "end_s": "530",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.467186484730344379467186484730344379467186484730344379467186484730344379467186484730344379467186485",
            "battery_end_kwh": "1.731075373619233268356075373619233268356075373619233268356075373619233268356075373619233268356075374",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "530",
            "end_s": "540",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.731075373619233268356075373619233268356075373619233268356075373619233268356075373619233268356075374",
            "battery_end_kwh": "1.994964262508122157244964262508122157244964262508122157244964262508122157244964262508122157244964263",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "540",
            "end_s": "550",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "1.994964262508122157244964262508122157244964262508122157244964262508122157244964262508122157244964263",
            "battery_end_kwh": "2.258853151397011046133853151397011046133853151397011046133853151397011046133853151397011046133853151",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.21",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "550",
            "end_s": "560",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.258853151397011046133853151397011046133853151397011046133853151397011046133853151397011046133853151",
            "battery_end_kwh": "2.52274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.53",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "560",
            "end_s": "570",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.52274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "2.786630929174788823911630929174788823911630929174788823911630929174788823911630929174788823911630929",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.85",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "570",
            "end_s": "580",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "2.786630929174788823911630929174788823911630929174788823911630929174788823911630929174788823911630929",
            "battery_end_kwh": "3.050519818063677712800519818063677712800519818063677712800519818063677712800519818063677712800519818",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.17",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "580",
            "end_s": "590",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.050519818063677712800519818063677712800519818063677712800519818063677712800519818063677712800519818",
            "battery_end_kwh": "3.314408706952566601689408706952566601689408706952566601689408706952566601689408706952566601689408707",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.49",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "590",
            "end_s": "600",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.314408706952566601689408706952566601689408706952566601689408706952566601689408706952566601689408707",
            "battery_end_kwh": "3.578297595841455490578297595841455490578297595841455490578297595841455490578297595841455490578297596",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.81",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "600",
            "end_s": "610",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.578297595841455490578297595841455490578297595841455490578297595841455490578297595841455490578297596",
            "battery_end_kwh": "3.842186484730344379467186484730344379467186484730344379467186484730344379467186484730344379467186485",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.13",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "610",
            "end_s": "620",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "3.842186484730344379467186484730344379467186484730344379467186484730344379467186484730344379467186485",
            "battery_end_kwh": "4.106075373619233268356075373619233268356075373619233268356075373619233268356075373619233268356075374",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.45",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "620",
            "end_s": "630",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "4.106075373619233268356075373619233268356075373619233268356075373619233268356075373619233268356075374",
            "battery_end_kwh": "4.369964262508122157244964262508122157244964262508122157244964262508122157244964262508122157244964263",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "630",
            "end_s": "640",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "4.369964262508122157244964262508122157244964262508122157244964262508122157244964262508122157244964263",
            "battery_end_kwh": "4.633853151397011046133853151397011046133853151397011046133853151397011046133853151397011046133853151",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "640",
            "end_s": "650",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "4.633853151397011046133853151397011046133853151397011046133853151397011046133853151397011046133853151",
            "battery_end_kwh": "4.89774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.41",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "650",
            "end_s": "660",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "4.89774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "5.161630929174788823911630929174788823911630929174788823911630929174788823911630929174788823911630929",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "660",
            "end_s": "670",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.161630929174788823911630929174788823911630929174788823911630929174788823911630929174788823911630929",
            "battery_end_kwh": "5.425519818063677712800519818063677712800519818063677712800519818063677712800519818063677712800519818",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "670",
            "end_s": "680",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.425519818063677712800519818063677712800519818063677712800519818063677712800519818063677712800519818",
            "battery_end_kwh": "5.689408706952566601689408706952566601689408706952566601689408706952566601689408706952566601689408707",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.37",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "680",
            "end_s": "690",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.689408706952566601689408706952566601689408706952566601689408706952566601689408706952566601689408707",
            "battery_end_kwh": "5.953297595841455490578297595841455490578297595841455490578297595841455490578297595841455490578297596",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.69",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "690",
            "end_s": "700",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "5.953297595841455490578297595841455490578297595841455490578297595841455490578297595841455490578297596",
            "battery_end_kwh": "6.217186484730344379467186484730344379467186484730344379467186484730344379467186484730344379467186485",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.01",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "700",
            "end_s": "710",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.217186484730344379467186484730344379467186484730344379467186484730344379467186484730344379467186485",
            "battery_end_kwh": "6.481075373619233268356075373619233268356075373619233268356075373619233268356075373619233268356075374",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.33",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "710",
            "end_s": "720",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.481075373619233268356075373619233268356075373619233268356075373619233268356075373619233268356075374",
            "battery_end_kwh": "6.744964262508122157244964262508122157244964262508122157244964262508122157244964262508122157244964263",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.65",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "720",
            "end_s": "730",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "6.744964262508122157244964262508122157244964262508122157244964262508122157244964262508122157244964263",
            "battery_end_kwh": "7.008853151397011046133853151397011046133853151397011046133853151397011046133853151397011046133853151",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.97",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "730",
            "end_s": "740",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.008853151397011046133853151397011046133853151397011046133853151397011046133853151397011046133853151",
            "battery_end_kwh": "7.27274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "740",
            "end_s": "750",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.27274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "7.536630929174788823911630929174788823911630929174788823911630929174788823911630929174788823911630929",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "750",
            "end_s": "760",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.536630929174788823911630929174788823911630929174788823911630929174788823911630929174788823911630929",
            "battery_end_kwh": "7.800519818063677712800519818063677712800519818063677712800519818063677712800519818063677712800519818",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.93",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "760",
            "end_s": "770",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "7.800519818063677712800519818063677712800519818063677712800519818063677712800519818063677712800519818",
            "battery_end_kwh": "8.064408706952566601689408706952566601689408706952566601689408706952566601689408706952566601689408707",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "770",
            "end_s": "780",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.064408706952566601689408706952566601689408706952566601689408706952566601689408706952566601689408707",
            "battery_end_kwh": "8.328297595841455490578297595841455490578297595841455490578297595841455490578297595841455490578297596",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "780",
            "end_s": "790",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.328297595841455490578297595841455490578297595841455490578297595841455490578297595841455490578297596",
            "battery_end_kwh": "8.592186484730344379467186484730344379467186484730344379467186484730344379467186484730344379467186485",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "790",
            "end_s": "800",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.592186484730344379467186484730344379467186484730344379467186484730344379467186484730344379467186485",
            "battery_end_kwh": "8.856075373619233268356075373619233268356075373619233268356075373619233268356075373619233268356075374",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.21",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "800",
            "end_s": "810",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "8.856075373619233268356075373619233268356075373619233268356075373619233268356075373619233268356075374",
            "battery_end_kwh": "9.119964262508122157244964262508122157244964262508122157244964262508122157244964262508122157244964263",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.53",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "810",
            "end_s": "820",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "9.119964262508122157244964262508122157244964262508122157244964262508122157244964262508122157244964263",
            "battery_end_kwh": "9.383853151397011046133853151397011046133853151397011046133853151397011046133853151397011046133853151",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.85",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "820",
            "end_s": "830",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "9.383853151397011046133853151397011046133853151397011046133853151397011046133853151397011046133853151",
            "battery_end_kwh": "9.64774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.17",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "830",
            "end_s": "840",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "9.64774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "9.911630929174788823911630929174788823911630929174788823911630929174788823911630929174788823911630929",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.49",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "840",
            "end_s": "850",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "9.911630929174788823911630929174788823911630929174788823911630929174788823911630929174788823911630929",
            "battery_end_kwh": "10.17551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.81",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "850",
            "end_s": "860",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.17551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "10.43940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.13",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "860",
            "end_s": "870",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.43940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "10.7032975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.45",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "870",
            "end_s": "880",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.7032975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "10.96718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "880",
            "end_s": "890",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "10.96718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "11.23107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "890",
            "end_s": "900",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.23107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "11.49496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.41",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "unavailable",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "900",
            "end_s": "910",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.49496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "battery_end_kwh": "11.75885315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "910",
            "end_s": "920",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "11.75885315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "battery_end_kwh": "12.02274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "920",
            "end_s": "930",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.02274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "12.28663092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.37",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "930",
            "end_s": "940",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.28663092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "battery_end_kwh": "12.55051981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.69",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "940",
            "end_s": "950",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.55051981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "12.81440870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.01",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "950",
            "end_s": "960",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "12.81440870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "13.0782975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.33",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "960",
            "end_s": "970",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.0782975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "13.34218648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.65",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "970",
            "end_s": "980",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.34218648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "13.60607537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.97",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "980",
            "end_s": "990",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.60607537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "13.86996426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "990",
            "end_s": "1000",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "13.86996426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "battery_end_kwh": "14.13385315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1000",
            "end_s": "1010",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "14.13385315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "battery_end_kwh": "14.39774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.93",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1010",
            "end_s": "1020",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "14.39774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "14.66163092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1020",
            "end_s": "1030",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "14.66163092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "battery_end_kwh": "14.92551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1030",
            "end_s": "1040",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "14.92551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "15.18940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1040",
            "end_s": "1050",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.18940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "15.4532975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.21",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1050",
            "end_s": "1060",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.4532975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "15.71718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1060",
            "end_s": "1070",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.71718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "15.98107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1070",
            "end_s": "1080",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "15.98107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "16.24496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1080",
            "end_s": "1090",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.24496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "battery_end_kwh": "16.50885315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1090",
            "end_s": "1100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.50885315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "battery_end_kwh": "16.77274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1100",
            "end_s": "1110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "16.77274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "17.03663092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1110",
            "end_s": "1120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.03663092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "battery_end_kwh": "17.30051981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1120",
            "end_s": "1130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.30051981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "17.56440870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.78",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1130",
            "end_s": "1140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.56440870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "17.8282975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.10",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1140",
            "end_s": "1150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "17.8282975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "18.09218648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.42",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1150",
            "end_s": "1160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "18.09218648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "18.35607537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.74",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1160",
            "end_s": "1170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "18.35607537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "18.61996426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.06",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1170",
            "end_s": "1180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "18.61996426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "battery_end_kwh": "18.88385315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.38",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1180",
            "end_s": "1190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "18.88385315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "battery_end_kwh": "19.14774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1190",
            "end_s": "1200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19.14774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "19.41163092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1200",
            "end_s": "1210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19.41163092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "battery_end_kwh": "19.67551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1210",
            "end_s": "1220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19.67551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "19.93940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.66",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1220",
            "end_s": "1230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "19.93940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "20.2032975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.98",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1230",
            "end_s": "1240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.2032975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "20.46718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.30",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1240",
            "end_s": "1250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.46718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "20.73107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.62",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1250",
            "end_s": "1260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.73107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "20.99496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.94",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1260",
            "end_s": "1270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "20.99496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "battery_end_kwh": "21.25885315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.26",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1270",
            "end_s": "1280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.25885315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "battery_end_kwh": "21.52274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1280",
            "end_s": "1290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.52274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "21.78663092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.90",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1290",
            "end_s": "1300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "21.78663092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "battery_end_kwh": "22.05051981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1300",
            "end_s": "1310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.05051981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "22.31440870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1310",
            "end_s": "1320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.31440870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "22.5782975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1320",
            "end_s": "1330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.5782975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "22.84218648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1330",
            "end_s": "1340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "22.84218648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "23.10607537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1340",
            "end_s": "1350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "23.10607537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "23.36996426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "36.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1350",
            "end_s": "1360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "23.36996426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "battery_end_kwh": "23.63385315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "37.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1360",
            "end_s": "1370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "23.63385315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "battery_end_kwh": "23.89774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "37.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1370",
            "end_s": "1380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "23.89774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "24.16163092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "37.78",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1380",
            "end_s": "1390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "24.16163092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "battery_end_kwh": "24.42551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "38.10",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1390",
            "end_s": "1400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "24.42551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "24.68940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "38.42",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1400",
            "end_s": "1410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "24.68940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "24.9532975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "38.74",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1410",
            "end_s": "1420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "24.9532975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "25.21718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "39.06",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1420",
            "end_s": "1430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "25.21718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "25.48107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "39.38",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1430",
            "end_s": "1440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "25.48107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "25.74496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "39.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1440",
            "end_s": "1450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "25.74496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "battery_end_kwh": "26.00885315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "40.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1450",
            "end_s": "1460",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "26.00885315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "battery_end_kwh": "26.27274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "40.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1460",
            "end_s": "1470",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "26.27274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "26.53663092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "40.66",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1470",
            "end_s": "1480",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "26.53663092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "battery_end_kwh": "26.80051981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "40.98",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1480",
            "end_s": "1490",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "26.80051981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "27.06440870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "41.30",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1490",
            "end_s": "1500",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "27.06440870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "27.3282975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "41.62",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1500",
            "end_s": "1510",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "27.3282975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "27.59218648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "41.94",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1510",
            "end_s": "1520",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "27.59218648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "27.85607537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "42.26",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1520",
            "end_s": "1530",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "27.85607537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "28.11996426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "42.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1530",
            "end_s": "1540",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "28.11996426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "battery_end_kwh": "28.38385315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "42.90",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1540",
            "end_s": "1550",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "28.38385315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "battery_end_kwh": "28.64774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "43.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1550",
            "end_s": "1560",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "28.64774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "28.91163092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "43.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1560",
            "end_s": "1570",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "28.91163092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "battery_end_kwh": "29.17551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "43.86",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1570",
            "end_s": "1580",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "29.17551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "29.43940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "44.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1580",
            "end_s": "1590",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "29.43940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "29.7032975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "44.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1590",
            "end_s": "1600",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "29.7032975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "29.96718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "44.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1600",
            "end_s": "1610",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "29.96718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "30.23107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "45.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1610",
            "end_s": "1620",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "30.23107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "30.49496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "45.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1620",
            "end_s": "1630",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "30.49496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "battery_end_kwh": "30.75885315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "45.79",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1630",
            "end_s": "1640",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "30.75885315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "battery_end_kwh": "31.02274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "46.11",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1640",
            "end_s": "1650",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "31.02274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "31.28663092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "46.43",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1650",
            "end_s": "1660",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "31.28663092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "battery_end_kwh": "31.55051981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "46.75",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1660",
            "end_s": "1670",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "31.55051981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "31.81440870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "47.07",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1670",
            "end_s": "1680",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "31.81440870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "32.0782975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "47.39",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1680",
            "end_s": "1690",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "32.0782975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "32.34218648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "47.71",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1690",
            "end_s": "1700",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "32.34218648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "32.60607537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "48.03",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1700",
            "end_s": "1710",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "32.60607537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "32.86996426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "48.35",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1710",
            "end_s": "1720",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "32.86996426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "battery_end_kwh": "33.13385315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "48.67",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1720",
            "end_s": "1730",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "33.13385315139701104613385315139701104613385315139701104613385315139701104613385315139701104613385315",
            "battery_end_kwh": "33.39774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "48.99",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1730",
            "end_s": "1740",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "33.39774204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "33.66163092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "49.31",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1740",
            "end_s": "1750",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "33.66163092917478882391163092917478882391163092917478882391163092917478882391163092917478882391163093",
            "battery_end_kwh": "33.92551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "49.63",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1750",
            "end_s": "1760",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "33.92551981806367771280051981806367771280051981806367771280051981806367771280051981806367771280051982",
            "battery_end_kwh": "34.18940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "49.95",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1760",
            "end_s": "1770",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "34.18940870695256660168940870695256660168940870695256660168940870695256660168940870695256660168940871",
            "battery_end_kwh": "34.4532975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "50.27",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1770",
            "end_s": "1780",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "34.4532975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782976",
            "battery_end_kwh": "34.71718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "50.59",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1780",
            "end_s": "1790",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "34.71718648473034437946718648473034437946718648473034437946718648473034437946718648473034437946718648",
            "battery_end_kwh": "34.98107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "50.91",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1790",
            "end_s": "1800",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "100",
            "battery_start_kwh": "34.98107537361923326835607537361923326835607537361923326835607537361923326835607537361923326835607537",
            "battery_end_kwh": "35.24496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "51.23",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "3.201754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0.01388888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0.2638888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888888889",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "charging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1152.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          }
        ],
        "events": [
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "utility",
            "value_kw": null,
            "sequence": 0,
            "origin": "scenario_event"
          },
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "generator",
            "value_kw": null,
            "sequence": 1,
            "origin": "scenario_event"
          },
          {
            "at_s": "500",
            "action": "asset_up",
            "target": "utility",
            "value_kw": null,
            "sequence": 2,
            "origin": "scenario_event"
          },
          {
            "at_s": "900",
            "action": "asset_up",
            "target": "generator",
            "value_kw": null,
            "sequence": 3,
            "origin": "scenario_event"
          }
        ],
        "summary": {
          "requested_it_kwh": "500",
          "served_it_kwh": "500",
          "unserved_it_kwh": "0",
          "grid_kwh": "512.2807017543859649122807017543859649122807017543859649122807017543859649122807017543859649122807018",
          "generator_kwh": "0",
          "distribution_loss_kwh": "26.31578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631578947",
          "battery_charge_loss_kwh": "2.222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222",
          "battery_discharge_loss_kwh": "6.497725795971410006497725795971410006497725795971410006497725795971410006497725795971410006497725796",
          "battery_stored_change_kwh": "-22.75503573749187784275503573749187784275503573749187784275503573749187784275503573749187784275503574",
          "unserved_duration_s": "0",
          "battery_final_kwh": "35.24496426250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426",
          "peak_unserved_kw": "0",
          "energy_balance_residual_kwh": "0",
          "grid_energy_charge": "51.23",
          "generator_energy_charge": "0.00",
          "total_incremental_energy_charge": "51.23",
          "cost_status": "illustrative",
          "service_status": "served_throughout",
          "interval_count": 180
        },
        "boundary": "Electrical supply, stored battery energy, conversion losses and served IT; cooling excluded",
        "limitations": [
          "No switching transient, protection study, cooling, workload queue or certification model.",
          "Generator starts on utility-asset unavailability only; downstream path faults do not request a start.",
          "Generator fuel is assumed sufficient for this horizon; its unit energy cost may be unknown.",
          "Initial stored battery energy is an opening balance; prior charging cost is excluded.",
          "Prices are illustrative inputs; costs exclude CAPEX and non-energy charges."
        ]
      }
    }
  ]
}