  "schema_version": 1,
  "lesson_id": "ride-through",
  "lesson_url": "https://khanlab.co.technology/learn/ride-through/",
  "engine_version": "2.0.1",
  "source_revision": "4878472c4d6c166c3dbd81aee292a0a56e89ffff",
  "result_unit": "s elapsed",
  "records": [
    {
      "configuration": "starting",
      "input": "100",
      "result": "607.8",
      "unit": "s elapsed",
      "calculation": {
        "schema_version": 2,
        "model": "single_load_electrical_continuity_v1",
        "engine_version": "2.0.1",
        "run_id": "7264f710596ef5aef30f",
        "input_sha256": "a11b0d4078daef9a79e07f7969940203c23ccaa800c0a2c60cc5853b0acacfd0",
        "mode": "SIMULATED",
        "quality": "synthetic_uncalibrated",
        "scenario": {
          "schema_version": 2,
          "id": "course-ride-through",
          "name": "3. Calculate battery ride-through",
          "currency": "USD",
          "duration_s": 1800,
          "step_s": 10,
          "it_demand_kw": "1000",
          "it_capacity_kw": "1000",
          "distribution_efficiency": "0.95",
          "tariff_per_kwh": "0.1",
          "generator_cost_per_kwh": null,
          "generator_start_delay_s": 30,
          "battery_capacity_kwh": "100",
          "battery_initial_kwh": "100",
          "battery_charge_kw": "0",
          "battery_charge_efficiency": "0.95",
          "battery_discharge_efficiency": "0.9",
          "source_ids": [
            "DEMO-ELECTRICAL-002",
            "EDU-POWER-001"
          ],
          "assets": [
            {
              "id": "utility",
              "name": "Utility feed",
              "kind": "utility",
              "capacity_kw": "1500",
              "failure_domains": [
                "utility-feed"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "generator",
              "name": "Standby generator",
              "kind": "generator",
              "capacity_kw": "1200",
              "failure_domains": [
                "generator-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "battery",
              "name": "UPS battery",
              "kind": "battery",
              "capacity_kw": "1200",
              "failure_domains": [
                "ups-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "main-bus",
              "name": "Main electrical bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "switchroom"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-a",
              "name": "Distribution A",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "a-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-b",
              "name": "Distribution B",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "b-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-bus",
              "name": "IT distribution bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "it-bus"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-load",
              "name": "Synthetic IT demand",
              "kind": "load",
              "capacity_kw": "2000",
              "failure_domains": [
                "it-hall"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            }
          ],
          "dependencies": [
            {
              "source": "utility",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "generator",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "battery",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-a",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-b",
              "relation": "feeds"
            },
            {
              "source": "path-a",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "path-b",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "it-bus",
              "target": "it-load",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "battery",
              "relation": "charges"
            }
          ],
          "events": [
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "generator",
              "value_kw": null
            },
            {
              "at_s": 900,
              "action": "asset_up",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 900,
              "action": "asset_up",
              "target": "generator",
              "value_kw": null
            }
          ]
        },
        "intervals": [
          {
            "start_s": "0",
            "end_s": "10",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "10",
            "end_s": "20",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "20",
            "end_s": "30",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.88",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "30",
            "end_s": "40",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.17",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "40",
            "end_s": "50",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "50",
            "end_s": "60",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.75",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "60",
            "end_s": "70",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "70",
            "end_s": "80",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "80",
            "end_s": "90",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.63",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "90",
            "end_s": "100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.92",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "100",
            "end_s": "110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "110",
            "end_s": "120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.51",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "120",
            "end_s": "130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.80",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "130",
            "end_s": "140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "140",
            "end_s": "150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.39",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "150",
            "end_s": "160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.68",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "160",
            "end_s": "170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.97",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "170",
            "end_s": "180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.26",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "180",
            "end_s": "190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.56",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "190",
            "end_s": "200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.85",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "200",
            "end_s": "210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "210",
            "end_s": "220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.43",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "220",
            "end_s": "230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "230",
            "end_s": "240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "240",
            "end_s": "250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.31",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "250",
            "end_s": "260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.60",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "260",
            "end_s": "270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "270",
            "end_s": "280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.19",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "280",
            "end_s": "290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.48",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "290",
            "end_s": "300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "100",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "300",
            "end_s": "310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "100",
            "battery_end_kwh": "96.7511371020142949967511371020142949967511371020142949967511371020142949967511371020142949967511371",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "310",
            "end_s": "320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "96.7511371020142949967511371020142949967511371020142949967511371020142949967511371020142949967511371",
            "battery_end_kwh": "93.5022742040285899935022742040285899935022742040285899935022742040285899935022742040285899935022742",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "320",
            "end_s": "330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "93.5022742040285899935022742040285899935022742040285899935022742040285899935022742040285899935022742",
            "battery_end_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "330",
            "end_s": "340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "90.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "87.00454840805717998700454840805717998700454840805717998700454840805717998700454840805717998700454841",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "340",
            "end_s": "350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "87.00454840805717998700454840805717998700454840805717998700454840805717998700454840805717998700454841",
            "battery_end_kwh": "83.75568551007147498375568551007147498375568551007147498375568551007147498375568551007147498375568551",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "350",
            "end_s": "360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "83.75568551007147498375568551007147498375568551007147498375568551007147498375568551007147498375568551",
            "battery_end_kwh": "80.50682261208576998050682261208576998050682261208576998050682261208576998050682261208576998050682261",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "360",
            "end_s": "370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "80.50682261208576998050682261208576998050682261208576998050682261208576998050682261208576998050682261",
            "battery_end_kwh": "77.25795971410006497725795971410006497725795971410006497725795971410006497725795971410006497725795971",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "370",
            "end_s": "380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "77.25795971410006497725795971410006497725795971410006497725795971410006497725795971410006497725795971",
            "battery_end_kwh": "74.00909681611435997400909681611435997400909681611435997400909681611435997400909681611435997400909682",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "380",
            "end_s": "390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "74.00909681611435997400909681611435997400909681611435997400909681611435997400909681611435997400909682",
            "battery_end_kwh": "70.76023391812865497076023391812865497076023391812865497076023391812865497076023391812865497076023392",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "390",
            "end_s": "400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "70.76023391812865497076023391812865497076023391812865497076023391812865497076023391812865497076023392",
            "battery_end_kwh": "67.51137102014294996751137102014294996751137102014294996751137102014294996751137102014294996751137102",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "400",
            "end_s": "410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "67.51137102014294996751137102014294996751137102014294996751137102014294996751137102014294996751137102",
            "battery_end_kwh": "64.26250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426250812",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "410",
            "end_s": "420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "64.26250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426250812",
            "battery_end_kwh": "61.01364522417153996101364522417153996101364522417153996101364522417153996101364522417153996101364522",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "420",
            "end_s": "430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "61.01364522417153996101364522417153996101364522417153996101364522417153996101364522417153996101364522",
            "battery_end_kwh": "57.76478232618583495776478232618583495776478232618583495776478232618583495776478232618583495776478233",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "430",
            "end_s": "440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "57.76478232618583495776478232618583495776478232618583495776478232618583495776478232618583495776478233",
            "battery_end_kwh": "54.51591942820012995451591942820012995451591942820012995451591942820012995451591942820012995451591943",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "440",
            "end_s": "450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "54.51591942820012995451591942820012995451591942820012995451591942820012995451591942820012995451591943",
            "battery_end_kwh": "51.26705653021442495126705653021442495126705653021442495126705653021442495126705653021442495126705653",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "450",
            "end_s": "460",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "51.26705653021442495126705653021442495126705653021442495126705653021442495126705653021442495126705653",
            "battery_end_kwh": "48.01819363222871994801819363222871994801819363222871994801819363222871994801819363222871994801819363",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "460",
            "end_s": "470",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "48.01819363222871994801819363222871994801819363222871994801819363222871994801819363222871994801819363",
            "battery_end_kwh": "44.76933073424301494476933073424301494476933073424301494476933073424301494476933073424301494476933073",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "470",
            "end_s": "480",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "44.76933073424301494476933073424301494476933073424301494476933073424301494476933073424301494476933073",
            "battery_end_kwh": "41.52046783625730994152046783625730994152046783625730994152046783625730994152046783625730994152046784",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "480",
            "end_s": "490",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "41.52046783625730994152046783625730994152046783625730994152046783625730994152046783625730994152046784",
            "battery_end_kwh": "38.27160493827160493827160493827160493827160493827160493827160493827160493827160493827160493827160494",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "490",
            "end_s": "500",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "38.27160493827160493827160493827160493827160493827160493827160493827160493827160493827160493827160494",
            "battery_end_kwh": "35.02274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "500",
            "end_s": "510",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "35.02274204028589993502274204028589993502274204028589993502274204028589993502274204028589993502274204",
            "battery_end_kwh": "31.77387914230019493177387914230019493177387914230019493177387914230019493177387914230019493177387914",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "510",
            "end_s": "520",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "31.77387914230019493177387914230019493177387914230019493177387914230019493177387914230019493177387914",
            "battery_end_kwh": "28.52501624431448992852501624431448992852501624431448992852501624431448992852501624431448992852501624",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "520",
            "end_s": "530",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "28.52501624431448992852501624431448992852501624431448992852501624431448992852501624431448992852501624",
            "battery_end_kwh": "25.27615334632878492527615334632878492527615334632878492527615334632878492527615334632878492527615335",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "530",
            "end_s": "540",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "25.27615334632878492527615334632878492527615334632878492527615334632878492527615334632878492527615335",
            "battery_end_kwh": "22.02729044834307992202729044834307992202729044834307992202729044834307992202729044834307992202729045",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "540",
            "end_s": "550",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "22.02729044834307992202729044834307992202729044834307992202729044834307992202729044834307992202729045",
            "battery_end_kwh": "18.77842755035737491877842755035737491877842755035737491877842755035737491877842755035737491877842755",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "550",
            "end_s": "560",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "18.77842755035737491877842755035737491877842755035737491877842755035737491877842755035737491877842755",
            "battery_end_kwh": "15.52956465237166991552956465237166991552956465237166991552956465237166991552956465237166991552956465",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "560",
            "end_s": "570",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "15.52956465237166991552956465237166991552956465237166991552956465237166991552956465237166991552956465",
            "battery_end_kwh": "12.28070175438596491228070175438596491228070175438596491228070175438596491228070175438596491228070175",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "570",
            "end_s": "580",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "12.28070175438596491228070175438596491228070175438596491228070175438596491228070175438596491228070175",
            "battery_end_kwh": "9.031838856400259909031838856400259909031838856400259909031838856400259909031838856400259909031838856",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "580",
            "end_s": "590",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "9.031838856400259909031838856400259909031838856400259909031838856400259909031838856400259909031838856",
            "battery_end_kwh": "5.782975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782975958",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "590",
            "end_s": "600",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "5.782975958414554905782975958414554905782975958414554905782975958414554905782975958414554905782975958",
            "battery_end_kwh": "2.53411306042884990253411306042884990253411306042884990253411306042884990253411306042884990253411306",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "600",
            "end_s": "607.8",
            "duration_s": "7.8",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "2.53411306042884990253411306042884990253411306042884990253411306042884990253411306042884990253411306",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
              "served_it_kwh": "2.166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1140350877192982456140350877192982456140350877192982456140350877192982456140350877192982456140350877",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.253411306042884990253411306042884990253411306042884990253411306042884990253411306042884990253411306",
              "battery_stored_change_kwh": "-2.53411306042884990253411306042884990253411306042884990253411306042884990253411306042884990253411306",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "607.8",
            "end_s": "617.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "617.8",
            "end_s": "627.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "627.8",
            "end_s": "637.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "637.8",
            "end_s": "647.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "647.8",
            "end_s": "657.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "657.8",
            "end_s": "667.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "667.8",
            "end_s": "677.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "677.8",
            "end_s": "687.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "687.8",
            "end_s": "697.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "697.8",
            "end_s": "707.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "707.8",
            "end_s": "717.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "717.8",
            "end_s": "727.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "727.8",
            "end_s": "737.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "737.8",
            "end_s": "747.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "747.8",
            "end_s": "757.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "757.8",
            "end_s": "767.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "767.8",
            "end_s": "777.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "777.8",
            "end_s": "787.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "787.8",
            "end_s": "797.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "797.8",
            "end_s": "807.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "807.8",
            "end_s": "817.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "817.8",
            "end_s": "827.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "827.8",
            "end_s": "837.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "837.8",
            "end_s": "847.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "847.8",
            "end_s": "857.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "857.8",
            "end_s": "867.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "867.8",
            "end_s": "877.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "877.8",
            "end_s": "887.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "887.8",
            "end_s": "897.8",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "897.8",
            "end_s": "900",
            "duration_s": "2.2",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "0.6111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
              "served_it_kwh": "0",
              "unserved_it_kwh": "0.6111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "2.2"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "900",
            "end_s": "910",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.06",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "910",
            "end_s": "920",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.36",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "920",
            "end_s": "930",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.65",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "930",
            "end_s": "940",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.94",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "940",
            "end_s": "950",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.23",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "950",
            "end_s": "960",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.53",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "960",
            "end_s": "970",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "970",
            "end_s": "980",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.11",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "980",
            "end_s": "990",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.40",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "990",
            "end_s": "1000",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1000",
            "end_s": "1010",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.99",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1010",
            "end_s": "1020",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.28",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1020",
            "end_s": "1030",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1030",
            "end_s": "1040",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.87",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1040",
            "end_s": "1050",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.16",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1050",
            "end_s": "1060",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.45",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1060",
            "end_s": "1070",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.74",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1070",
            "end_s": "1080",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.04",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1080",
            "end_s": "1090",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.33",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1090",
            "end_s": "1100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.62",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1100",
            "end_s": "1110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.91",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1110",
            "end_s": "1120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.20",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1120",
            "end_s": "1130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1130",
            "end_s": "1140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.79",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1140",
            "end_s": "1150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.08",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1150",
            "end_s": "1160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.37",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1160",
            "end_s": "1170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.67",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1170",
            "end_s": "1180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.96",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1180",
            "end_s": "1190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1190",
            "end_s": "1200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1200",
            "end_s": "1210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.84",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1210",
            "end_s": "1220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.13",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1220",
            "end_s": "1230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.42",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1230",
            "end_s": "1240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.71",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1240",
            "end_s": "1250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.01",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1250",
            "end_s": "1260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.30",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1260",
            "end_s": "1270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.59",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1270",
            "end_s": "1280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.88",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1280",
            "end_s": "1290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1290",
            "end_s": "1300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.47",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1300",
            "end_s": "1310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.76",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1310",
            "end_s": "1320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1320",
            "end_s": "1330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.35",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1330",
            "end_s": "1340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.64",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1340",
            "end_s": "1350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.93",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1350",
            "end_s": "1360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1360",
            "end_s": "1370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.51",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1370",
            "end_s": "1380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.81",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1380",
            "end_s": "1390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.10",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1390",
            "end_s": "1400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.39",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1400",
            "end_s": "1410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.68",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1410",
            "end_s": "1420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.98",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1420",
            "end_s": "1430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.27",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1430",
            "end_s": "1440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.56",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1440",
            "end_s": "1450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.85",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1450",
            "end_s": "1460",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.15",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1460",
            "end_s": "1470",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.44",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1470",
            "end_s": "1480",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1480",
            "end_s": "1490",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1490",
            "end_s": "1500",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.32",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1500",
            "end_s": "1510",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1510",
            "end_s": "1520",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.90",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1520",
            "end_s": "1530",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.19",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1530",
            "end_s": "1540",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.49",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1540",
            "end_s": "1550",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.78",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1550",
            "end_s": "1560",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.07",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1560",
            "end_s": "1570",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.36",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1570",
            "end_s": "1580",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.65",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1580",
            "end_s": "1590",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.95",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1590",
            "end_s": "1600",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.24",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1600",
            "end_s": "1610",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.53",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1610",
            "end_s": "1620",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1620",
            "end_s": "1630",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.12",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1630",
            "end_s": "1640",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.41",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1640",
            "end_s": "1650",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1650",
            "end_s": "1660",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.99",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1660",
            "end_s": "1670",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1670",
            "end_s": "1680",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1680",
            "end_s": "1690",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.87",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1690",
            "end_s": "1700",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.16",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1700",
            "end_s": "1710",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1710",
            "end_s": "1720",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.75",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1720",
            "end_s": "1730",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.04",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1730",
            "end_s": "1740",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.33",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1740",
            "end_s": "1750",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.63",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1750",
            "end_s": "1760",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.92",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1760",
            "end_s": "1770",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.21",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1770",
            "end_s": "1780",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1780",
            "end_s": "1790",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.80",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1790",
            "end_s": "1800",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          }
        ],
        "events": [
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "utility",
            "value_kw": null,
            "sequence": 0,
            "origin": "scenario_event"
          },
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "generator",
            "value_kw": null,
            "sequence": 1,
            "origin": "scenario_event"
          },
          {
            "at_s": "607.8",
            "action": "battery_depleted",
            "target": "battery",
            "origin": "simulation"
          },
          {
            "at_s": "900",
            "action": "asset_up",
            "target": "utility",
            "value_kw": null,
            "sequence": 2,
            "origin": "scenario_event"
          },
          {
            "at_s": "900",
            "action": "asset_up",
            "target": "generator",
            "value_kw": null,
            "sequence": 3,
            "origin": "scenario_event"
          }
        ],
        "summary": {
          "requested_it_kwh": "500",
          "served_it_kwh": "418.8333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
          "unserved_it_kwh": "81.16666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
          "grid_kwh": "350.877192982456140350877192982456140350877192982456140350877192982456140350877192982456140350877193",
          "generator_kwh": "0",
          "distribution_loss_kwh": "22.04385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754385965",
          "battery_charge_loss_kwh": "0",
          "battery_discharge_loss_kwh": "10",
          "battery_stored_change_kwh": "-100",
          "unserved_duration_s": "292.2",
          "battery_final_kwh": "0",
          "peak_unserved_kw": "1000",
          "energy_balance_residual_kwh": "0",
          "grid_energy_charge": "35.09",
          "generator_energy_charge": "0.00",
          "total_incremental_energy_charge": "35.09",
          "cost_status": "illustrative",
          "service_status": "unserved_load",
          "interval_count": 181
        },
        "boundary": "Electrical supply, stored battery energy, conversion losses and served IT; cooling excluded",
        "limitations": [
          "No switching transient, protection study, cooling, workload queue or certification model.",
          "Generator starts on utility-asset unavailability only; downstream path faults do not request a start.",
          "Generator fuel is assumed sufficient for this horizon; its unit energy cost may be unknown.",
          "Initial stored battery energy is an opening balance; prior charging cost is excluded.",
          "Prices are illustrative inputs; costs exclude CAPEX and non-energy charges."
        ]
      }
    },
    {
      "configuration": "challenge",
      "input": "50",
      "result": "453.9",
      "unit": "s elapsed",
      "calculation": {
        "schema_version": 2,
        "model": "single_load_electrical_continuity_v1",
        "engine_version": "2.0.1",
        "run_id": "5303e03c55bbad457de0",
        "input_sha256": "0db72b981fa59c8a566e5610fd8627f4c623baeb8bb2662d22c5cae246a2b8b9",
        "mode": "SIMULATED",
        "quality": "synthetic_uncalibrated",
        "scenario": {
          "schema_version": 2,
          "id": "course-ride-through",
          "name": "3. Calculate battery ride-through",
          "currency": "USD",
          "duration_s": 1800,
          "step_s": 10,
          "it_demand_kw": "1000",
          "it_capacity_kw": "1000",
          "distribution_efficiency": "0.95",
          "tariff_per_kwh": "0.1",
          "generator_cost_per_kwh": null,
          "generator_start_delay_s": 30,
          "battery_capacity_kwh": "100",
          "battery_initial_kwh": "50",
          "battery_charge_kw": "0",
          "battery_charge_efficiency": "0.95",
          "battery_discharge_efficiency": "0.9",
          "source_ids": [
            "DEMO-ELECTRICAL-002",
            "EDU-POWER-001"
          ],
          "assets": [
            {
              "id": "utility",
              "name": "Utility feed",
              "kind": "utility",
              "capacity_kw": "1500",
              "failure_domains": [
                "utility-feed"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "generator",
              "name": "Standby generator",
              "kind": "generator",
              "capacity_kw": "1200",
              "failure_domains": [
                "generator-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "battery",
              "name": "UPS battery",
              "kind": "battery",
              "capacity_kw": "1200",
              "failure_domains": [
                "ups-control"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "main-bus",
              "name": "Main electrical bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "switchroom"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-a",
              "name": "Distribution A",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "a-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "path-b",
              "name": "Distribution B",
              "kind": "distribution",
              "capacity_kw": "700",
              "failure_domains": [
                "b-room",
                "shared-controls"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-bus",
              "name": "IT distribution bus",
              "kind": "bus",
              "capacity_kw": "1800",
              "failure_domains": [
                "it-bus"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            },
            {
              "id": "it-load",
              "name": "Synthetic IT demand",
              "kind": "load",
              "capacity_kw": "2000",
              "failure_domains": [
                "it-hall"
              ],
              "source_ids": [
                "DEMO-ELECTRICAL-002"
              ]
            }
          ],
          "dependencies": [
            {
              "source": "utility",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "generator",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "battery",
              "target": "main-bus",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-a",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "path-b",
              "relation": "feeds"
            },
            {
              "source": "path-a",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "path-b",
              "target": "it-bus",
              "relation": "feeds"
            },
            {
              "source": "it-bus",
              "target": "it-load",
              "relation": "feeds"
            },
            {
              "source": "main-bus",
              "target": "battery",
              "relation": "charges"
            }
          ],
          "events": [
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 300,
              "action": "asset_down",
              "target": "generator",
              "value_kw": null
            },
            {
              "at_s": 900,
              "action": "asset_up",
              "target": "utility",
              "value_kw": null
            },
            {
              "at_s": 900,
              "action": "asset_up",
              "target": "generator",
              "value_kw": null
            }
          ]
        },
        "intervals": [
          {
            "start_s": "0",
            "end_s": "10",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "10",
            "end_s": "20",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "20",
            "end_s": "30",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "0.88",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "30",
            "end_s": "40",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.17",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "40",
            "end_s": "50",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "50",
            "end_s": "60",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "1.75",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "60",
            "end_s": "70",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "70",
            "end_s": "80",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.34",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "80",
            "end_s": "90",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.63",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "90",
            "end_s": "100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "2.92",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "100",
            "end_s": "110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "110",
            "end_s": "120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.51",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "120",
            "end_s": "130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "3.80",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "130",
            "end_s": "140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "140",
            "end_s": "150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.39",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "150",
            "end_s": "160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.68",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "160",
            "end_s": "170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "4.97",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "170",
            "end_s": "180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.26",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "180",
            "end_s": "190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.56",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "190",
            "end_s": "200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "5.85",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "200",
            "end_s": "210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.14",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "210",
            "end_s": "220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.43",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "220",
            "end_s": "230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "6.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "230",
            "end_s": "240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "240",
            "end_s": "250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.31",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "250",
            "end_s": "260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.60",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "260",
            "end_s": "270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "7.89",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "270",
            "end_s": "280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.19",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "280",
            "end_s": "290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.48",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "290",
            "end_s": "300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "50",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "ready",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "300",
            "end_s": "310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "50",
            "battery_end_kwh": "46.7511371020142949967511371020142949967511371020142949967511371020142949967511371020142949967511371",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "310",
            "end_s": "320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "46.7511371020142949967511371020142949967511371020142949967511371020142949967511371020142949967511371",
            "battery_end_kwh": "43.5022742040285899935022742040285899935022742040285899935022742040285899935022742040285899935022742",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "320",
            "end_s": "330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "43.5022742040285899935022742040285899935022742040285899935022742040285899935022742040285899935022742",
            "battery_end_kwh": "40.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "330",
            "end_s": "340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "40.25341130604288499025341130604288499025341130604288499025341130604288499025341130604288499025341131",
            "battery_end_kwh": "37.00454840805717998700454840805717998700454840805717998700454840805717998700454840805717998700454841",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "340",
            "end_s": "350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "37.00454840805717998700454840805717998700454840805717998700454840805717998700454840805717998700454841",
            "battery_end_kwh": "33.75568551007147498375568551007147498375568551007147498375568551007147498375568551007147498375568551",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "350",
            "end_s": "360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "33.75568551007147498375568551007147498375568551007147498375568551007147498375568551007147498375568551",
            "battery_end_kwh": "30.50682261208576998050682261208576998050682261208576998050682261208576998050682261208576998050682261",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "360",
            "end_s": "370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "30.50682261208576998050682261208576998050682261208576998050682261208576998050682261208576998050682261",
            "battery_end_kwh": "27.25795971410006497725795971410006497725795971410006497725795971410006497725795971410006497725795971",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "370",
            "end_s": "380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "27.25795971410006497725795971410006497725795971410006497725795971410006497725795971410006497725795971",
            "battery_end_kwh": "24.00909681611435997400909681611435997400909681611435997400909681611435997400909681611435997400909682",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "380",
            "end_s": "390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "24.00909681611435997400909681611435997400909681611435997400909681611435997400909681611435997400909682",
            "battery_end_kwh": "20.76023391812865497076023391812865497076023391812865497076023391812865497076023391812865497076023392",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "390",
            "end_s": "400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "20.76023391812865497076023391812865497076023391812865497076023391812865497076023391812865497076023392",
            "battery_end_kwh": "17.51137102014294996751137102014294996751137102014294996751137102014294996751137102014294996751137102",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "400",
            "end_s": "410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "17.51137102014294996751137102014294996751137102014294996751137102014294996751137102014294996751137102",
            "battery_end_kwh": "14.26250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426250812",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "410",
            "end_s": "420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "14.26250812215724496426250812215724496426250812215724496426250812215724496426250812215724496426250812",
            "battery_end_kwh": "11.01364522417153996101364522417153996101364522417153996101364522417153996101364522417153996101364522",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "420",
            "end_s": "430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "11.01364522417153996101364522417153996101364522417153996101364522417153996101364522417153996101364522",
            "battery_end_kwh": "7.764782326185834957764782326185834957764782326185834957764782326185834957764782326185834957764782326",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "430",
            "end_s": "440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "7.764782326185834957764782326185834957764782326185834957764782326185834957764782326185834957764782326",
            "battery_end_kwh": "4.515919428200129954515919428200129954515919428200129954515919428200129954515919428200129954515919428",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "440",
            "end_s": "450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "4.515919428200129954515919428200129954515919428200129954515919428200129954515919428200129954515919428",
            "battery_end_kwh": "1.26705653021442495126705653021442495126705653021442495126705653021442495126705653021442495126705653",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.3248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "battery_stored_change_kwh": "-3.248862897985705003248862897985705003248862897985705003248862897985705003248862897985705003248862898",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "450",
            "end_s": "453.9",
            "duration_s": "3.9",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "battery_charge_kw": "0",
            "battery_start_kwh": "1.26705653021442495126705653021442495126705653021442495126705653021442495126705653021442495126705653",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "1.083333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
              "served_it_kwh": "1.083333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
              "unserved_it_kwh": "0",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.05701754385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754386",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0.126705653021442495126705653021442495126705653021442495126705653021442495126705653021442495126705653",
              "battery_stored_change_kwh": "-1.26705653021442495126705653021442495126705653021442495126705653021442495126705653021442495126705653",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "discharging",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "453.9",
            "end_s": "463.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "463.9",
            "end_s": "473.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "473.9",
            "end_s": "483.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "483.9",
            "end_s": "493.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "493.9",
            "end_s": "503.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "503.9",
            "end_s": "513.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "513.9",
            "end_s": "523.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "523.9",
            "end_s": "533.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "533.9",
            "end_s": "543.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "543.9",
            "end_s": "553.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "553.9",
            "end_s": "563.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "563.9",
            "end_s": "573.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "573.9",
            "end_s": "583.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "583.9",
            "end_s": "593.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "593.9",
            "end_s": "603.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "603.9",
            "end_s": "613.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "613.9",
            "end_s": "623.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "623.9",
            "end_s": "633.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "633.9",
            "end_s": "643.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "643.9",
            "end_s": "653.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "653.9",
            "end_s": "663.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "663.9",
            "end_s": "673.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "673.9",
            "end_s": "683.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "683.9",
            "end_s": "693.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "693.9",
            "end_s": "703.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "703.9",
            "end_s": "713.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "713.9",
            "end_s": "723.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "723.9",
            "end_s": "733.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "733.9",
            "end_s": "743.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "743.9",
            "end_s": "753.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "753.9",
            "end_s": "763.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "763.9",
            "end_s": "773.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "773.9",
            "end_s": "783.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "783.9",
            "end_s": "793.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "793.9",
            "end_s": "803.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "803.9",
            "end_s": "813.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "813.9",
            "end_s": "823.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "823.9",
            "end_s": "833.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "833.9",
            "end_s": "843.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "843.9",
            "end_s": "853.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "853.9",
            "end_s": "863.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "863.9",
            "end_s": "873.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "873.9",
            "end_s": "883.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "883.9",
            "end_s": "893.9",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "0",
              "unserved_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "10"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "893.9",
            "end_s": "900",
            "duration_s": "6.1",
            "requested_it_kw": "1000",
            "served_it_kw": "0",
            "unserved_it_kw": "1000",
            "electrical_source_kw": "0",
            "grid_kw": "0",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "8.77",
            "energy": {
              "requested_it_kwh": "1.694444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
              "served_it_kwh": "0",
              "unserved_it_kwh": "1.694444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444444",
              "grid_kwh": "0",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "6.1"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "unavailable",
              "generator": "unavailable",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "unserved"
            },
            "warnings": [
              "UNSERVED_IT_LOAD",
              "UTILITY_UNAVAILABLE",
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "0"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "0"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "0"
              }
            ]
          },
          {
            "start_s": "900",
            "end_s": "910",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.06",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "910",
            "end_s": "920",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.36",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "920",
            "end_s": "930",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.65",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "930",
            "end_s": "940",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "9.94",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "940",
            "end_s": "950",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.23",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "950",
            "end_s": "960",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.53",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "960",
            "end_s": "970",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "10.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "970",
            "end_s": "980",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.11",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "980",
            "end_s": "990",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.40",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "990",
            "end_s": "1000",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1000",
            "end_s": "1010",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "11.99",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1010",
            "end_s": "1020",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.28",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1020",
            "end_s": "1030",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.57",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1030",
            "end_s": "1040",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "12.87",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1040",
            "end_s": "1050",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.16",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1050",
            "end_s": "1060",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.45",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1060",
            "end_s": "1070",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "13.74",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1070",
            "end_s": "1080",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.04",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1080",
            "end_s": "1090",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.33",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1090",
            "end_s": "1100",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.62",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1100",
            "end_s": "1110",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "14.91",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1110",
            "end_s": "1120",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.20",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1120",
            "end_s": "1130",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1130",
            "end_s": "1140",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "15.79",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1140",
            "end_s": "1150",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.08",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1150",
            "end_s": "1160",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.37",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1160",
            "end_s": "1170",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.67",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1170",
            "end_s": "1180",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "16.96",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1180",
            "end_s": "1190",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.25",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1190",
            "end_s": "1200",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.54",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1200",
            "end_s": "1210",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "17.84",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1210",
            "end_s": "1220",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.13",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1220",
            "end_s": "1230",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.42",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1230",
            "end_s": "1240",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "18.71",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1240",
            "end_s": "1250",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.01",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1250",
            "end_s": "1260",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.30",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1260",
            "end_s": "1270",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.59",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1270",
            "end_s": "1280",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "19.88",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1280",
            "end_s": "1290",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.18",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1290",
            "end_s": "1300",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.47",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1300",
            "end_s": "1310",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "20.76",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1310",
            "end_s": "1320",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.05",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1320",
            "end_s": "1330",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.35",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1330",
            "end_s": "1340",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.64",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1340",
            "end_s": "1350",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "21.93",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1350",
            "end_s": "1360",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.22",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1360",
            "end_s": "1370",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.51",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1370",
            "end_s": "1380",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "22.81",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1380",
            "end_s": "1390",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.10",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1390",
            "end_s": "1400",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.39",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1400",
            "end_s": "1410",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.68",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1410",
            "end_s": "1420",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "23.98",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1420",
            "end_s": "1430",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.27",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1430",
            "end_s": "1440",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.56",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1440",
            "end_s": "1450",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "24.85",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1450",
            "end_s": "1460",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.15",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1460",
            "end_s": "1470",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.44",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1470",
            "end_s": "1480",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "25.73",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1480",
            "end_s": "1490",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.02",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1490",
            "end_s": "1500",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.32",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1500",
            "end_s": "1510",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.61",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1510",
            "end_s": "1520",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "26.90",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1520",
            "end_s": "1530",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.19",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1530",
            "end_s": "1540",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.49",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1540",
            "end_s": "1550",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "27.78",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1550",
            "end_s": "1560",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.07",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1560",
            "end_s": "1570",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.36",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1570",
            "end_s": "1580",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.65",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1580",
            "end_s": "1590",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "28.95",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1590",
            "end_s": "1600",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.24",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1600",
            "end_s": "1610",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.53",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1610",
            "end_s": "1620",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "29.82",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1620",
            "end_s": "1630",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.12",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1630",
            "end_s": "1640",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.41",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1640",
            "end_s": "1650",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.70",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1650",
            "end_s": "1660",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "30.99",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1660",
            "end_s": "1670",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.29",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1670",
            "end_s": "1680",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.58",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1680",
            "end_s": "1690",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "31.87",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1690",
            "end_s": "1700",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.16",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1700",
            "end_s": "1710",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.46",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1710",
            "end_s": "1720",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "32.75",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1720",
            "end_s": "1730",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.04",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1730",
            "end_s": "1740",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.33",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1740",
            "end_s": "1750",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.63",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1750",
            "end_s": "1760",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "33.92",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1760",
            "end_s": "1770",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.21",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1770",
            "end_s": "1780",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.50",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1780",
            "end_s": "1790",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "34.80",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          },
          {
            "start_s": "1790",
            "end_s": "1800",
            "duration_s": "10",
            "requested_it_kw": "1000",
            "served_it_kw": "1000",
            "unserved_it_kw": "0",
            "electrical_source_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "grid_kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579",
            "generator_kw": "0",
            "battery_discharge_kw": "0",
            "battery_charge_kw": "0",
            "battery_start_kwh": "0",
            "battery_end_kwh": "0",
            "it_capacity_margin_kw": "0",
            "grid_energy_charge_to_date": "35.09",
            "energy": {
              "requested_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "served_it_kwh": "2.777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777777778",
              "unserved_it_kwh": "0",
              "grid_kwh": "2.923976608187134502923976608187134502923976608187134502923976608187134502923976608187134502923976608",
              "generator_kwh": "0",
              "distribution_loss_kwh": "0.1461988304093567251461988304093567251461988304093567251461988304093567251461988304093567251461988304",
              "battery_charge_loss_kwh": "0",
              "battery_discharge_loss_kwh": "0",
              "battery_stored_change_kwh": "0",
              "unserved_duration_s": "0"
            },
            "energy_balance_residual_kwh": "0",
            "asset_states": {
              "utility": "available",
              "generator": "standby",
              "battery": "empty",
              "main-bus": "available",
              "path-a": "available",
              "path-b": "available",
              "it-bus": "available",
              "it-load": "served"
            },
            "warnings": [
              "BATTERY_EMPTY"
            ],
            "feed_flows_kw": [
              {
                "source": "utility",
                "target": "main-bus",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              },
              {
                "source": "generator",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "battery",
                "target": "main-bus",
                "kw": "0"
              },
              {
                "source": "main-bus",
                "target": "path-a",
                "kw": "700"
              },
              {
                "source": "main-bus",
                "target": "path-b",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "path-a",
                "target": "it-bus",
                "kw": "700"
              },
              {
                "source": "path-b",
                "target": "it-bus",
                "kw": "352.6315789473684210526315789473684210526315789473684210526315789473684210526315789473684210526315789"
              },
              {
                "source": "it-bus",
                "target": "it-load",
                "kw": "1052.631578947368421052631578947368421052631578947368421052631578947368421052631578947368421052631579"
              }
            ]
          }
        ],
        "events": [
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "utility",
            "value_kw": null,
            "sequence": 0,
            "origin": "scenario_event"
          },
          {
            "at_s": "300",
            "action": "asset_down",
            "target": "generator",
            "value_kw": null,
            "sequence": 1,
            "origin": "scenario_event"
          },
          {
            "at_s": "453.9",
            "action": "battery_depleted",
            "target": "battery",
            "origin": "simulation"
          },
          {
            "at_s": "900",
            "action": "asset_up",
            "target": "utility",
            "value_kw": null,
            "sequence": 2,
            "origin": "scenario_event"
          },
          {
            "at_s": "900",
            "action": "asset_up",
            "target": "generator",
            "value_kw": null,
            "sequence": 3,
            "origin": "scenario_event"
          }
        ],
        "summary": {
          "requested_it_kwh": "500",
          "served_it_kwh": "376.0833333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333333",
          "unserved_it_kwh": "123.9166666666666666666666666666666666666666666666666666666666666666666666666666666666666666666666667",
          "grid_kwh": "350.877192982456140350877192982456140350877192982456140350877192982456140350877192982456140350877193",
          "generator_kwh": "0",
          "distribution_loss_kwh": "19.79385964912280701754385964912280701754385964912280701754385964912280701754385964912280701754385965",
          "battery_charge_loss_kwh": "0",
          "battery_discharge_loss_kwh": "5",
          "battery_stored_change_kwh": "-50",
          "unserved_duration_s": "446.1",
          "battery_final_kwh": "0",
          "peak_unserved_kw": "1000",
          "energy_balance_residual_kwh": "0",
          "grid_energy_charge": "35.09",
          "generator_energy_charge": "0.00",
          "total_incremental_energy_charge": "35.09",
          "cost_status": "illustrative",
          "service_status": "unserved_load",
          "interval_count": 181
        },
        "boundary": "Electrical supply, stored battery energy, conversion losses and served IT; cooling excluded",
        "limitations": [
          "No switching transient, protection study, cooling, workload queue or certification model.",
          "Generator starts on utility-asset unavailability only; downstream path faults do not request a start.",
          "Generator fuel is assumed sufficient for this horizon; its unit energy cost may be unknown.",
          "Initial stored battery energy is an opening balance; prior charging cost is excluded.",
          "Prices are illustrative inputs; costs exclude CAPEX and non-energy charges."
        ]
      }
    }
  ]
}