DATACENTER TWIN LAB

Lesson 03 / 12 · Finite storage

Calculate battery ride-through

Does half the stored energy give half the ride-through duration?

Run this browser lesson →

Predict before you run

Write down your prediction, then change only the input below. In the interactive lesson, compare the starting case with the challenge and export a worksheet to retain your reasoning.

The two lesson configurations
InputStarting valueChallenge value
Initial battery100 kWh50 kWh

Reported quantity: s elapsed. The live control accepts 0–100 kWh.

Worked answer

Charging is disabled in this lesson. 100 kWh delivers 85.5 kWh after the two losses: 307.8 s of ride-through. 50 kWh gives 153.9 s, so depletion is at 453.9 s elapsed.

Reproduce the configuration

Starting case assumptions
IT demand / simulated duration1000 kW / 1800 s
Opening battery / energy capacity100 kWh / 100 kWh
Charging power limit0 kW
Charge / discharge efficiency0.95 / 0.9
Distribution efficiency0.95
Generator start delay30 s

Scheduled events

The browser lesson applies its configuration to the generator_failure preset. Open it above, run the starting case, switch to the challenge, and use “Verify against Python” to compare complete results. Use the worksheet export to keep the prediction, completed inputs and answer together.

Sources and verification

Original material by Mohammad Rezwan Khan, engine 1.0.0. Synthetic teaching cases; no facility calibration or independent external reproduction has been established. Annual PUE planning and outage continuity are different calculations. Full scope and evidence.